The ―Destn‖ numbers signify DF1 node addresses that would be entered into the SLC 5/04’s MSG instruction. The IP

address of the EtherNet IP device that the SLC 5/04 is going to send or read data from is entered under the ―IP Address‖

row corresponding to the selected ―Destn‖ node address. In the example, node address ―45‖ is mapped to

192.168.001.101 (MW100). Note that to communicate with ControlLogix or CompactLogix systems or other devices that

utilize CIP (DX Advanced, MW100), node addresses 45 thru 49 must be used. After entering the destination IP address,

click on the ―Utility Settings‖ tab.

Under ―COM Port‖, select the com port on the PC, which will be used to upload/download to the 1761

-NET-ENI. When

first taken out of the box, the 1761-NET-ENI’s (Series B or higher) RS232 baud rate is set to ―Auto‖. In this example, the

baud rate to ―38400‖

(the fastest setting allowed in the SLC 5/04 Channel 0 configuration). The click on the ―ENI IP Addr‖

tab.

At this point, with the PC connected to the 1761-NET-ENI, under the ―Save To‖ area on the right, select ―ENI ROM‖ (the

configuration may also be saved to a file for future use, or in the 1761-NET-ENI’s RAM. If the configuration is stored in

RAM, it will be lost upon power down). Once the download is complete, the 1761-NET-ENI is now ready for use.