Remote control input, Remote control input -17 – Yokogawa µR20000 User Manual

Page 30

Advertising
background image

3-17

SM 04P01B01-01E

Testing

3

When the /F1 Option is Not Installed

Relay

Relay No.

I01-I06

I01-I06

When the /F1 Option Is Installed

Relay

Relay No.

I01-I04

I01-I04

Chart Paper End Output Relay

I05

FAIL Output Relay

FAIL

Output Relays Other Than the FAIL Output Relay
Select the relay number to test and confirm that it is open between the NO and C
relay output terminals. Press the

key. The relay is energized. Check that it is

closed between relay output terminals NO and C.

FAIL Output Relay
Select FAIL in the relay number selection screen and confirm it is closed between
relay output terminals NO and C. Press the

key. The relay is deenergized

approximately four seconds thereafter. Confirm that it is open between relay output
terminals NO and C.

You cannot operate the recorder after execution of FAIL output relay test. Turn OFF
the recorder, then turn it back ON again.

Remote Control Input

Overview

This test is performed when the /R1 option is specified. It is performed for all remote
control input terminals.

Procedures

1.

Turn ON the power switch while pressing the

MENU

and

CH UP

keys. Menu = A/D

Adjust is displayed.

2.

Select Menu = Test, and press the

key.

3.

Choose Test = Remote and press the

key.

4.

Connect the remote control input terminal under test to the C terminal and press
the

key.

The remote control input terminal condition confirmation screen appears.
Confirm that the display of the corresponding remote control input terminal is 1.

Remote Status
00000

5.

Press the

ESC/?

key to return to the Test = Remote screen.

Repeat the above steps 4 and 5 for all input terminals.

* Select using the key. You can hold down the SHIFT key while pressing key to reverse the
key’s action.

3.4 Test Procedures