Adjusting the pen position, Adjusting the pen position -5 – Yokogawa µR20000 User Manual

Page 36

Advertising
background image

4-5

SM 04P02B01-01E

Adjustments

4

8.

When all pen adjustments are finished, select Mode = End, then press the
key.

Mode=End

9.

With End = Store displayed, press the

key.

The adjusted value is saved.

End=Store

Concluding Adjustments
10.

Select Menu = End, then press the

key. You are returned to the operation

mode.

Menu=End

Note

If Error is displayed in the adjustment results screen, this most likely indicates that the pen

cannot move normally through the full scale. Check the operation of the pen, then perform the

adjustment again.

Adjusting the Pen Position

Overview

This is an adjustment of the pen position to make the recording position 0 to 180 mm.
Each pen is adjusted individually. The adjustment is performed when the recording
accuracy is outside the criterion, or when internal components have been replaced.
Conditions
• Use a standard pen (or equivalent).

*

A “standard pen” is one whose tip does not fluctuate more than ±0.1 mm.

• The adjustment matches the Zero position to the 0% position of the z-fold chart

paper.

• It also aligns the Full position from the 0% of the z-fold chart paper to the 180 mm

position.

• For measurement, use a Glass scale (or equivalent).

Criterion

Adjustment criterion: within ±0.1 mm

Procedure

1.

Install the pen into the pen arm.

2.

Press the

MENU

and

CH UP

keys while turning ON the power. Menu = A/D

Adjust is displayed.

3.

Select Menu = Pos Adjust, then press the

key.

The Zero/Full selection screen appears.

Menu=Pos Adjust

4.2 Adjustments to the Pen Model

* Select using the key. To enter numerical values, move the cursor to the entry point using the
key. Select the value using the key. You can hold down the SHIFT key while pressing
key or key to reverse the key’s action.

Advertising
This manual is related to the following products: