Venting, Vertically vented unit heaters (category i) – Sterling TF User Manual

Page 13

Advertising
background image

13

VENTING

Observe the following precautions when venting the unit:
1. Use flue pipe of the same size as the flue

connections on the gas unit heater (See Table 1).
All heaters should be vented with single or double
wall vent, a factory built chimney, or a lined brick
and mortar chimney that has been constructed in
accordance with the National Building Code. Type B
vent should only be used for vertical rise portions of
a Category I vent pipe system. Type B vent should
not be used for horizontal runs of vent pipe.

2. Provide as long a vertical run of fl ue pipe at the gas

unit heater as possible. A minimum of 5 feet (1.5m)
of vertical fl ue is required. The top of the vent pipe
should extend at least 2 feet (0.61m) above the
highest point on the roof. Install a weather cap over
the vent opening. Consideration should be made for
anticipated snow depth.

3. Slope horizontal runs upward from the gas unit

heater at least 1/4-inch per foot (21mm/m) minimum.
Horizontal runs should not exceed 75% of the
vertical height of the vent pipe, or chimney, above
the fl ue pipe connection, up to a maximum length
of 10 feet (3m). Horizontal portions of the venting
system shall be supported at minimum intervals of
4 feet (1.2m). (See Figure 6) In Canada, support at
minimum intervals of 3 feet (1m).

4. Use as few elbows as possible.

5. Avoid running vent pipe through unheated spaces.

6. When this cannot be avoided, insulate the pipe to

prevent condensation of moisture on the walls of the
pipe.

7. Do not damper the fl ue piping. Failure to open such

a damper prior to operating the gas unit heater will
result in the spillage of flue gas into the occupied
space.

8. Avoid installing units in areas under negative

pressure due to large exhaust fans or air
conditioning. When required, a fl ue vent fan should
be installed in accordance with the instructions
included with the fan.

9. Vent connectors serving Category I and Category

II heaters shall not be connected into any portion of
mechanical draft systems operating under positive
pressure.

ANSI now organizes vented
appliances into four categories.

Venting Categories

Non

Condensing

Condensing

Negative
Vent

I

II

Pressure

Positive
Vent

III IV

Pressure

VERTICALLY VENTED UNIT HEATERS (CATEGORY I)

Category I
Includes non-condensing
appliances with negative vent
pressure, like the traditional
atmospheric unit heater.

Category II
Groups condensing appliances
with negative vent pressure.

Category III
Appliances are non-condensing
and operate with a positive vent
pressure.

Category IV
Covers condensing appliances with
positive vent pressure.

NOTICE: Category II and IV do
not apply to equipment specifi ed
within this manual.

All unit heaters must be vented! All Venting installations shall be in accordance with the latest edition of Part 7,
Venting of Equipment of the National Fuel Gas Code, ANSI Z223.1 (NFPA 54), or applicable provisions of local
building codes. Refer to page 15 for Canadian installations. Refer to Figures 6, 7, 8A, 8B, 9A and 9B.

CARBON MONOXIDE! Your venting system must not be blocked by any snow, snow

drifts, or any foreign matter. Inspect your venting system to ensure adequate ventilation exists at all
times! Failure to heed these warnings could result in Carbon Monoxide Poisoning (symptoms include
grogginess, lethargy, inappropriate tiredness, or fl u-like symptoms).

Do not damper or add heat recovery devices to the fl ue piping. Failure to open such a damper prior to operating
gas unit will result in the spillage of fl ue gas into the occupied space.

Advertising
This manual is related to the following products:

GF