Customer ____________________________________ Job Name & Number _________________________

PRE-INSPECTION INFORMATION

With power and gas off.

Type of Equip:

Unit Heater

Serial Number

_________________________ Model Number __________________________

Name Plate Voltage:

_____________

Name Plate Amperage: _____________

Type of Gas:

Natural

LP

Tank Capacity _______ lbs.

Rating: _ _____ BTU @ ____ °F

_______ kg

_ _____ kw @ ____ °C

Are all panels, doors, vent caps in place?

Has the unit suffered any external damage?

Damage ______________________________

Does the gas piping and electric wiring appear to be installed in a professional manner?

Has the gas and electric been inspected by the local authority having jurisdiction?

Is the gas supply properly sized for the equipment?

Were the installation instructions followed when the equipment was installed?

Have all fi eld installed controls been installed?

Do you understand all the controls on this equipment? If not, contact your wholesaler or rep.

(DO NOT START this equipment unless you fully understand the controls.)

GAS EQUIPMENT

START-UP

GENERAL

With power and gas off.

Make certain all packing has been removed.

Tighten all electrical terminals and connections.

Check all fans & blowers for free movement.

Check all controls for proper settings.

FAN

With power and gas off.

Check voltage. L1_____ L2_____ L3_____

Check rotation of main propeller(s).

Check motor amps. L1_____ L2_____ L3_____

Remarks:

_____________________________________________

__________________________________________________
__________________________________________________

GAS HEATING

With power and gas on.

Inlet gas pressure.

____ inch WC or ____ kPa

Burner ignition.

Manifold gas pressure. ____ inch WC or ____ kPa

Cycle fi restat and/or freezestat.

Check electronic modulation. Set at: __________

Cycle and check all other controls not listed.

Check operation of remote panel.

Entering air temp. _____ °F or ____ °C

Discharge air temp. (high fi re) ____ °F. or ____ °C

External static pressure _________ inch WC

Cycle by thermostat or operating control.

Combustion readings:

Carbon

Monoxide:______PPM

Carbon

Dioxide:______%