Installation (continued) – Sterling TF User Manual

Page 6

Advertising
background image

6

INSTALLATION (continued)

Table 2 - Heat Throw Data

Standard Heater

30° Nozzle

60° Nozzle

90° Nozzle

Degree

of

Nozzle

Distance From

Floor to Bottom

of Unit "H" - Feet

(m)

UNIT SIZE BTU/Hr

100,000

125,000

150,000

175,000

200,000

250,000

300,000

350,000

400,000

Approximate Distance of Heat Throw - Feet (Meters)

None

8

60

65

70

75

80

90

105

110

120

(2.4)

(18.3)

(19.8)

(21.3)

(22.9)

(24.4)

(27.4)

(32.0)

(33.5)

(36.6)

10

54

56

60

64

68

78

90

95

100

(3.0)

(16.5)

(17.1)

(18.3)

(19.5)

(20.7)

(23.8)

(27.4)

(29.0)

(30.5)

12

44

46

49

57

61

68

80

84

90

(3.7)

(13.4)

(14.0)

(14.9)

(17.4)

(18.6)

(20.7)

(24.4)

(25.6)

(27.4)

15

NR

NR

45

49

52

60

70

74

80

(4.6)

(13.7)

(14.9)

(15.8)

(18.3)

(21.3)

(22.6)

(24.4)

20

NR

NR

NR

NR

46

54

63

66

70

(6.1)

(14.0)

(16.5)

(19.2)

(20.1)

(21.3)

30°

8

65

70

75

80

85

95

115

120

125

(2.4)

(19.8)

(21.3)

(22.9)

(24.4)

(25.9)

(29.0)

(35.1)

(36.6)

(38.1)

10

57

60

64

68

72

86

99

105

110

(3.0)

(17.4)

(18.3)

(19.5)

(20.7)

(21.9)

(26.2)

(30.2)

(32.0)

(33.5)

12

50

54

57

60

64

77

88

94

100

(3.7)

(15.2)

(16.5)

(17.4)

(18.3)

(19.5)

(23.5)

(26.8)

(28.7)

(30.5)

15

NR

45

48

50

53

64

74

79

84

(4.6)

(13.7)

(14.6)

(15.2)

(16.2)

(19.5)

(22.6)

(24.1)

(25.6)

20

NR

NR

NR

44

47

58

66

71

75

(6.1)

(13.4)

(14.3)

(17.7)

(20.1)

(21.6)

(22.9)

60°

8

75

80

85

90

95

110

125

130

138

(2.4)

(22.9)

(24.4)

(25.9)

(27.4)

(29.0)

(33.5)

(38.1)

(39.6)

(42.1)

10

65

70

75

79

83

95

109

115

120

(3.0)

(19.8)

(21.3)

(22.9)

(24.1)

(25.3)

(29.0)

(33.2)

(35.1)

(36.6)

12

60

64

68

72

76

84

100

103

108

(3.7)

(18.3)

(19.5)

(20.7)

(21.9)

(23.2)

(25.6)

(30.5)

(31.4)

(32.9)

15

50

54

56

61

65

71

85

88

94

(4.6)

(15.2)

(16.5)

(17.1)

(18.6)

(19.8)

(21.6)

(25.9)

(26.8)

(28.7)

20

NR

49

52

55

59

65

77

81

85

(6.1)

(14.9)

(15.8)

(16.8)

(18.0)

(19.8)

(23.5)

(24.7)

(25.9)

90°*

15

30 x 25

35 x 30

40 x 35

45 x 40

50 x 40

60 x 45

70 x 45

80 x 50

100 x 50

(4.6)

(9.1) (7.6)

(10.7) (9.1)

(12.2) (10.7)

(13.7) (12.2)

(15.2) (12.2)

(18.3) (13.7)

(21.3) (13.7)

(24.4) (15.2)

(30.5) (15.2)

20

NR

NR

NR

NR

40 x 35

56 x 40

65 x 40

70 x 45

80 x 45

(6.1)

(12.2) (10.7)

(17.1) (12.2)

(19.8) (12.2)

(21.3) (13.7)

(24.4) (13.7)

25

NR

NR

NR

NR

NR

50 x 35

60 x 35

65 x 40

75 x 40

(7.6)

(15.2) (10.7)

(18.3) (10.7)

(19.8) (12.2)

(22.9) (12.2)

30

NR

NR

NR

NR

NR

NR

55 x 35

60 x 35

65 x 40

(9.1)

(16.8) (10.7)

(18.3) (10.7)

(19.8) (12.2)

* It is not recommended to mount a unit with a 90° nozzle under 10 feet.
Notes: 1. All throw data fi gures are approximations. Allowances should be made for optimum performance, altitude, etc.

2. NR - Units not recommended at these mounting heights.

3. 30°, 60° and 90° nozzles are shipped unassembled.