TUBULAR UNIT HEATER
HIGH ALTITUDE DERATION
This Tubular Unit Heater has been manufactured utilizing
standard burner orifi ces and a normal manifold pressure
setting as per the specifi cations shown on your unit rating
plate.

All unit deration must be done through fi eld adjustments
by a qualifi ed technician. Once the proper adjustments

Table 6A

Altitude

Manifold Pressure

BTU Output

1

Natural Gas

2

Liquid Propane

3

Feet

Meters

Inches WC

Pa

Inches WC

Pa

Percentage

0-2,000

0-610

3.5

872

10

2,491

100%

2,001-3,000

611-915

3.2

797

9.2

2,292

96%

3,001-4,000

916-1,220

2.9

722

8.4

2,092

92%

4,001-5,000

1,221-1,525

2.7

673

7.7

1,918

88%

5,001-6,000

1,526-1,830

2.4

598

7

1,744

84%

6,001-7,000

1,831-2,135

2.2

548

6.4

1,594

80%

7,001-8,000

2,136-2,440

2

498

5.7

1,420

76%

8,001-9,000

2,441-2,745

1.8

448

5.1

1,270

72%

9,001-10,000

2,746-3,045

1.6

399

4.6

1,145

68%

Notes:

1. Deration based on ANSI Z223.1 (NFPA 54).

2. Table based on heating value of 1,050 BTU/Cu. feet at sea level.

3. Table based on heating value of 2,500 BTU/Cu. feet at sea level.

4. Consult local utility for actual heating value.

Altitude

Manifold Pressure

BTU Output

1

Natural Gas

2

Liquid Propane

3

Feet

Meters

Inches WC

Pa

Inches WC

Pa

Percentage

0-2,000

0-610

3.5

872

10

2,491

100%

2,001-3,000

611-915

3.2

797

9.2

2,292

96%

3,001-4,000

916-1,220

2.9

722

8.4

2,092

92%

4,001-4,500

1,221-1,371

2.8

697

7.9

1,968

90%

Notes:

1. Deration based on CGA 2.17-M91

2. Table based on heating value of 1,050 BTU/Cu. feet at sea level.

3. Table based on heating value of 2,500 BTU/Cu. feet at sea level.

4. Consult local utility for actual heating value.

High Altitude Deration - United States

High Altitude Deration - Canada

are made in the fi eld, attach label #J17-06459 to the unit,
and record adjusted manifold pressure, altitude of the
unit installation and the technician’s name and date on
the label using a permanent marker.

Refer to Installation Instruction section on Adjustments-
Gas Input Rate for adjusting the manifold pressure.