Mammoth V-Cube Slim F-Series Sizes 180 to 350 User Manual

Page 12

Advertising
background image

Mammoth V-Cube Slim IOM, MAMM-VCS-IOM-4FA (October 2013) 12

Electrical

Electrical Terminals
Tighten all electrical terminals per the torque value listed

on the connector. Electrical terminals are located within

the main unit control panel. Where no torque value is

given, use the tightening torques provided in this manual.

See “Electrical Terminal Tightening Torques” on page

16.

WARNING! Loose electrical terminals can

lead to erratic unit operation and arcing which

may cause fires. Tighten all electrical ter-

minals before unit startup. Be careful not to

over-tighten to avoid stripping out threads..

Motor Protector Settings
Before startup, adjust the overload setting on all motor

protectors as follows. They are located within the unit

electrical panel. See Figure 10.
1. Switch to the off position all motor protectors.
2. For motors and pumps, adjust the setting to match

the amps (FLA) listed on the motor nameplate.

3. For compressors and VFDs, adjust the setting as

indicated on the electrical wiring diagram provided

with your unit.

Figure 10: Motor Protectors

Adjust motor protector amp settings to match electrical

schematics or motor nameplates

Control Settings

Verify that all control jumper positions, time delay

relay settings, baud rates and control temperatures

and/or pressure settings match those indicated on

the electrical wiring diagram, as applicable. Refer to

the wiring schematics provided with your unit for loca-

tions and settings.

Verify that high and low static pressure safety settings

match those indicated on the electrical wiring diagram.

They are typically set at 3.5 inches w.c. each. Record the

values on the Startup Report form.

Refrigerant Piping

Mammoth V-Cube Slim units with DX cooling are shipped

fully charged with refrigerant from the factory. No piping

connections are needed and no field charging is required

prior to operation of the system. Check the following prior

to startup:

Verify that all pressure lines are free from the com-

pressors – i.e., not contacting or rubbing against

them – to prevent damage from vibration and friction.

Pressure line coils should have a distance between

each coil of at least one inch.

Verify that all pipe clamps have the rubber lining

intact and are secure.

Verify that all compressor service valves are open.

Startup: Power On

With the main power control panel door closed, switch on

the main power to the unit. Then carry out the following

procedures.

WARNING! Electric shock and moving equip-

ment hazard. Can cause severe injury or

death. Use extreme caution when inspecting

or servicing equipment with electrical power

supplied to the unit. Per OSHA 29 CFR

1910.333 (c)(2): “Only qualified persons may

work on electric circuit parts or equipment

that have not been de-energized. Such per-

sons shall be capable of working safely on

energized circuits and shall be familiar with

the proper use of special precautionary tech-

niques, personal protective equipment, insu-

lating and shielding materials, and insulated

tools.”

Electrical
Supply Power

Verify that the measured supply voltage matches the

rated voltage on the unit nameplate. The nameplate

is located on the electrical panel door. Record volt-

ages on the startup form.

Motor Rotation

Verify that all fans, blowers and pumps are rotating

in the correct direction. This can be accomplished

by shutting off the motors individually, using each

motor’s overload protector shut-off switch, then

observing the direction of rotation as you start them

back up.

Check for proper rotation of each compressor using

a phase rotation meter. Also verify that the unit phase

Advertising