Disassembly and Assembly

General Guidelines

The Mammoth V Cube Slim Split is engineered to be

disassembled in the field and moved through 36” doors

into position then reassembled without breaking into the

refrigeration circuits. Only qualified personel experienced

in operation and maintenance of HVAC equipment should

perform these procedures.

WARNING! This equipment presents hazards

of electricity, rotating parts, sharp edges,

heat and weight. Failure to read and follow

these instructions can result in property dam-

age, severe personal injury or death. This

equipment must be installed by experienced,

trained personnel only.

WARNING! A mechanical lift is required to

move or lift all sections of a V-Cube Slim™

unit. Do not attempt to move or lift sections

without a mechanical lift. Failure to do so can

result in equipment damage, severe personal

injury or death.
WARNING! Lifting the entire unit (blower

section, coil section, etc.) using lifting lugs,

eye bolts or straps attached to the top of the

unit can result in serious damage to the unit,

personal injury or death.Lifting the entire unit

should only be done using a forklift or a strap-

ping spreader bar mechanism attached to the

base of the unit.
WARNING! All utilities (water, electric, and

communication cables) must be removed

prior to unit disassembly. Follow approved

lockout/tagout procedures before any disas-

sembly of the unit. Failure to do so can result

in electric shock, equipment damage, severe

personal injury, or death.

IMPORTANT! All blower wiring is correctly

phased at the factory and must be re-wired

correctly upon re-assembly for correct com-

pressor and blower operation. Mark all wires

and pull through knockouts using care not

to scrape the insulation of the wiring when

separating sections. If the wire insulation or

wire jacket is torn during the disassembly/

re-assembly procedure, replace the wire. Do

not use wire that is missing insulation. Con-

trol and sensor wiring uses Molex plugs for

proper polarity.

Figure 1: Unit As Shipped

Welded steel base - do not detach

Figure 1 shows the unit as shipped from the factory. Fig-

ure 2 shows an exploded view of the unit, equipped with

coil cabinets and 2” x 4“ filter racks. Note that the coil

cabinets and refrigeration sections are resting on welded

steel bases. These bases are an integral part of the sub-

assemblies and must not be removed.

IMPORTANT! The welded steel bases are

integral to subassembly stability and mobility.

Do not detach!

Figure 2: Exploded View

FANWALL section

Coil cabinet

End piping

assembly

Filter Rack

Main

chassis

Main electrical

panel

Mechanical lifting equipment is necessary to dismantle

and relocate the V Cube Slim Split. This unit will weigh

between 1800 and 3400 pounds depending on options

and features built into the unit at the factory.