Mammoth V-Cube Slim IOM, MAMM-VCS-IOM-4FA (October 2013) 6

Mechanical lifting equipment is also required to remove

the sub assemblies from the main chassis. Subassem-

blies weigh a minimum of 205 pounds and as much as

1500 pounds each.

Wiring

All low voltage wires are connected using quick-connect

plugs. NEMA does not allow quick-connect plugs for

power (high voltage) wiring. For this reason, all power

wires have raw ends and are ‘hardwired’ to terminal

blocks in the unit and require handtools for removal.

These power wires must be labeled prior to removal to

avoid problems.

Piping

All water piping is iron with grooved (Victualic

®

) connec-

tions.
Refrigeration circuits are copper pipe and do not require

any disassembly and reassembly.

Main Electrical Panel Removal

The main electrical panel is removed as follows.
1. Unplug the wiring harness that connects the EPiC™

keypad, reset buttons and selector switches from the

panel door to the main electrical panel.

2. Remove the panel door by lifting it from its hinges.

Carefully set it away from the unit to help prevent

damage during the remaining disassembly process.

3. Unplug all control wiring harnesses that run from the

main electrical panel to the main cabinet section. All

wiring connecting the main electrical panel to the unit

passes through knockouts on the left inside corner.

These plugs are labeled for correct re-installation.

4. Disconnect all high voltage wiring to the fan motors.
5. Verify that all electrical connections to the unit from

the control panel have been disconnected.

6. Support the electrical panel from above or below to

prevent it from falling once the connecting bolts have

been removed.

7. Loosen and remove the section bolts that fasten the

main electrical panel to the main cabinet sections, as

shown in Figure 3.

8. Set the main electrical panel aside, away from the

unit to help prevent damage during the remaining dis-

assembly process.

Figure 3: Main Electrical Panel Removal

Remove

mounting

bolts

Filter Rack and Coil Cabinet Removal

The coil cabinet and filter rack can be removed from the

main chassis, as follows. See Figure 4 for fastener loca-

tions.
1. Remove the filter rack from the coil cabinet by screw-

ing out the fasteners from the four corners of the rack.

IMPORTANT! Filter rack mounting bolts are

a specific length so as to not contact the coil

behind the bulkhead. If any are lost, replace-

ment bolts must be the same length.

Figure 4: Filter Rack and Coil Cabinet Removal

Filter rack

fasteners

Coil cabinet

fasteners