AMX Incandescent Dimmer Module RDM-INC User Manual

Installation sheet, Rdm-inc incandescent dimmer module 2400 w

Advertising
background image

Installation Sheet

RDM-INC Incandescent Dimmer Module

2400 W

The RDM-INC Incandescent Dimming Module is designed for use with the
RDA series of enclosures, in a AMX Lighting™ modular digital dimming
system. It is a standard 2400 W incandescent dimmer. It can dim incandes-
cent lights, cold-cathode, neon and two-wire dimmable ballasts. The RDM-
INC module's 120, 240, and 277 VAC ratings are CE, UL, and C-UL
approved.

RDM-INC UL and C-UL Ratings:

•

120 VAC, 50/60 Hz, 2400 W

•

240/277 VAC, 50/60 Hz, 2400 W

Suggested Dimmed Loads:

•

Incandescent

•

Low-voltage

•

Neon, cold-cathode

•

Two-wire, phase-controlled ballast

Specifications:

•

Dimensions (HW): 10.0" x 2.75" (25.4 cm x 6.985 cm)

•

Phase dependant

•

Use wires rated at 75°C (167°F)

•

Torque terminals to 7 in-lbs. (0.8 N/M)

•

Max. wire size: 10 AWG (4 mm²)

•

Wire stripping length: 0.28" (7 mm)

•

Weight: 3.7 lbs. (1.67 kg)

•

BTU/hr: 300

•

Control current: 45 mA @ 12 VDC

•

Choke: 350 µS Rise time @ 120 VAC

175 µS Rise time @ 240 VAC

Caution: Pre-Installation Notes:

•

All Class 1 wiring must be connected to proper terminals.

•

All control wiring must be connected to proper terminals.

•

Disconnect power while installing or connecting unit.

•

Keep top and bottom air vents clear at all times.

•

Test loads for shorts before connecting.

•

Use low voltage wires with a 300 volt rating or greater.

•

Use field installed copper conductors.

•

Run all low-voltage and control wires away from heat producing parts

of the dimmer.

•

Each dimming circuit must have a separate neutral connection.

•

All electrical ratings are for continuous duty.

•

AC lighting loads only.

•

For indoor use only.

•

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-INC to the AMX Lighting Master

Lighting Application Drawing

FIG. 1 RDM-INC

350µS
Choke

Line In

Line Out

Low-voltage control
wiring: 4-pin
connector to AMX
Lighting master
controller

20 A power device

High-voltage
connections

Mounting
points

FIG. 2 Connecting the RDM-INC to the AMX Lighting Master

FIG. 3 Sample wiring diagram

Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)

RDM-INC four-pin module connector

4-pin plug from a RDM series module

Note: The 4-pin plugs from the module
connector to the 4-pin connector on the
master (black plug cover facing up).

2 (-)

1 (+)

Neutral

Load

Neutral

Load

Neon lights
(cold-cathode, on/off)

Two-wire dimmable ballast

All neutrals are common
to the Neutral block in the
enclosure. Provide a
separate neutral for each
load.

Load

Line in
(HOT)

Circuit breaker
panel

Advertising