0 troubleshooting guide – Hired-Hand Universal Ray Tube Heaters: AG1 Series User Manual

Page 14

Advertising
background image

14

4.0

Troubleshooting Guide

4.0

Troubleshooting Guide

Continued on page 16.

AG1

Series

4.0

Troubleshooting Guide

Is the blower

obstructed?

Replace circuit board.

Does the ignitor warm

up and glow red?

Is the ignitor

physically

damaged?

Check voltage at ignitor during

ignition sequence (usually 30-

45 seconds after power to the

heater). Is it 120V?

Is the inlet or the outlet of the unit

obstructed (i.e., ice, birds nest, dirt,

flapper cap stuck closed, etc.) ?

Turn up thermostat

Does the fan

blower turn on?

Is the power at the

heater 120V?

Find the source of the electrical problem

between panel/thermostat and heater.

No

Yes

Remove obstruction

and lubricate fan.

No

Yes

Does the switch

light energize?

Yes

Is the light burnt out?

If so, replace.

No

No

Yes

Remove obstruction.

No

No

No

No

Yes

Yes

Replace ignitor.

Does valve light

energize?

Yes

Does the burner

ignite at all?

No

The circuit board and/or wiring

harness may be faulty and

needs to be replaced.

No

Yes

Replace faulty light.

Does valve open?

Yes

Yes

No

No

Yes

Advertising