NOTICE

Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed
during normal operation or the heater’s built-in safety mechanisms will be compromised.

17

4.0

Troubleshooting Guide

AG1

Series

Check to make sure gas pressure is within minimum and

maximum inputs, as indicated on burner rating plate.

Is gas pressure OK?

Were the gas lines purged of air?

Is the heater properly

grounded? Is the heater’s

polarity correct?

With micrometer, check

amperage at flame rod. Is it

greater than .4 microamps?

Check to make sure flame

sensor wire is OK. If so,

then replace circuit board.

Sensing rod is faulty or flame

is weak. Check to make sure

heater is operating at proper

gas pressure as indicated on

burner rating plate and then, if

needed, replace sensing rod.

Replace gas valve.

Yes

Correct problem.

Correct problem.

No

No

Yes

Yes

No

Purge gas line.

No

Yes

Confirm manifold pressure is

correct and/or gas orifice is not

plugged and is the correct size.