Hired-Hand Super-Savers (Forced Air Heaters) XL: SS-225-XL User Manual

Page 12

Advertising
background image

4801-5101

Rev

6-09

Page

12

of

26

Super Saver XL CE Heater

9. Loosen and remove the Orifice from the

12.7mm (1/2

″) pipe.

10. Apply pipe sealant to threads and reinstall the

new Orifice to the 12.7mm (1/2”) pipe. Replace
with the appropriate orifice for the new gas type
(Refer to Table 1).

NOTE: Ensure the tapered portion of the Orifice

points straight upward when installed to the
Gas Valve Assembly.

NOTE: Extra care should be taken to avoid turning

the pipe too far into the orifice. The pipe
should not restrict gas flow through the
orifice. A drill bit may be used as a stop-
guide if placed down through the Orifice
opening while threading the Orifice onto
the pipe. When the Orifice is properly
threaded onto the pipe, remove the drill bit
from the Orifice opening and ensure the
drill bit is removed before continuing
assembly.

11. Place the Gas Valve assembly with the Orifice

inside the Burner and allow the Gas Valve to
rest in the support bracket.

12. Install the machine screw thru the cabinet

bottom and into the bottom of the Orifice.
Tighten securely.

13. Apply pipe sealant to the threads and snugly

reinstall the ball valve, elbow, and 19mm (¾”)
M-to-M Pipe to the Gas Valve.

14. Reconnect the wires to the Gas Valve

assembly and ensure the wires are connected
to the proper terminals.

15. Apply pipe sealant to the threads of the Ball

Valve and connect the gas supply hose.

16. Turn the main gas supply ON.
17. Turn the Ball Valve to the ON position.
18. Check for gas leaks. (A soap and water

mixture works well.) Allow all areas to
completely dry.

19. Connect the heater to the power source.
20. Turn the toggle switch, located on the control

panel, to the ON position.

7.3 Adjust

the

Manifold

Pressure













Qualified Gas Technician Use Only!

1. Turn the toggle switch, located on the control

panel, to the OFF position.

2. Disconnect heater from the power source.

3. Turn the Ball Valve to the CLOSED position.
4. Turn OFF gas supply at source.
5. Completely loosen pressure tap and remove

regulator screw metal cap on gas valve.

NOTE: Do not remove the plastic regulator

adjustment screw beneath the metal cap.

6. Fit a gas pressure gauge on the pressure tap of

the gas valve. NOTE: A standard barbed fitting
may be required for this connection.

7. Reconnect gas, power supply, and turn the Ball

Valve ON.

8. Start heater and monitor the supply and

operating pressures.


9. Check supply pressure to ensure supply pressure

is within the heater’s operating limits (See Table
1, Gas/Air Requirements
).

10. Adjust the gas valve regulator to set the

operating pressure as specified in Table 1,
Gas/Air Requirements
. The plastic regulator
adjustment screw is already sealed after
adjustment.

11. Replace the regulator screw metal cap.
12. Turn OFF heater.
13. Remove gas pressure gauge and tighten the

pressure tap securely.

14. Verify proper heater operation and perform gas

leak test at the Pressure Tap.

Regulator

Honeywell VR8615 Gas Valve

Gas OUT

Pressure Tap

Gas IN

F

F

i

i

g

g

u

u

r

r

e

e

1

1

1

1