Chapter 3

46

Seed Hawk™ Viper Pro™ Installation & Operation Manual

Node Settings Screen (Page 2)

Touch within Data Box 2 and then select the Next button on the first Node Settings screen to access the

following settings.

Valve Cal

Enter the appropriate valve cal value for the valve used to turn product application on or off. Raven

recommends using the following initial values for the valve cal.

These values are good starting points and will generally yield adequate results, however, the valve cal should

be refined for the individual control valves installed on your specific machine.

Note:

Refer to Appendix D, Calculating Calibrations for Liquid and Granular Applications, for more
information on calculating your valve calibration.

Valve Cal 2

This setting is currently not used. This setting must remain at zero.

Fan/Pump Cal

The fan cal is used for granular applications only.

For the fan cal, enter the number of counts sensed in one revolution of the fan, if so equipped. For the pump

cal, enter the number of counts sensed in one revolution of the pump, if so equipped.

Min PW

Use the Min PW (Pulse Width) feature to set the minimum desired RPM or hydraulic output (zero point or

shutoff point) for a Pulse Width Modulated (PWM) control valve.

Valve Type

Calibration Number

Standard Valve

2123

Fast or Fast Close Valve (C-F or C-FC)

743

PWM or PWM Close Valve (C-P or C-PC)

43

Motor Control Node (Select Standard Valve)

123