Installation initial start-up and operation – Star Water Systems FB12DCC (Flint & Walling) User Manual

Page 3

Advertising
background image

3

© Copyright 2013. All rights reserved.

INSTALLATION

INITIAL START-UP AND OPERATION

1. Test the installation for leaks by running water into the sump

allowing for normal operation of the primary pump.

2. Check the control charger. The “red” power on light will be

lit when the unit is plugged into the 115V wall outlet. The

“yellow/green” light will indicate the condition of the battery.

3. Disconnect primary pump before touching any component

in the sump pit.

4. Lift float switch. The DC backup pump will run and the alarm

will sound. Lower float switch immediately after pump has

started running. Pump is running dry during initial check

out for several seconds.

CAUTION

Continuous dry

running may cause overheating and damage the pump

seals. Upon release of the float switch, the pump will shut

off. Press the reset button to turn the alarm off.

5. Complete the final testing of your installation by disconnecting

the power to the primary pump and the control charger by

removing the plugs from the 115V wall outlets. Run water

into the sump until the DC backup pump is activated by

the float switch. Check all connections for leaks.

6. Push alarm reset switch when pump is running. This will

silence the alarm. The pump will continue to run.

7. Reconnect the control charger and your primary pump to

the AC wall outlets. The primary pump should come on

and lower the water level in the sump back to the normal

operating level and shut off. Both primary and backup

systems are now ready for use.

8. The battery charged and charging LED’s will alternate

during normal charging operation.

12. If the old primary pump discharge piping is being replaced

with PVC piping, duplicate the old pipe dimensions and use

the existing drainage connection. If the primary pump and

backup pump is a new installation, the drainage connection

must be determined and the discharge pipes fitted

accordingly. Solvent weld the upper portion of the discharge

pipe into the PVC tee outlet (see figures 1 and 2). Connect

the discharge pipe into the drainage connection. The pipe

must be supported from above to ensure adequate support

for the pump assembly. Reinstall pumps in sump pit with

discharge back to its original position.

13. Install DC control charger (see figure 3) by using the wall

bracket and anchors provided. If more convenient, the

control charger may be set on a nearby shelf or ledge. The

control charger should be located 3 or 4 ft. above the sump.

To reduce noise from vibration, it is recommended that the

charger be anchored with the wall bracket provided.

14. Connect the leads from the control charger to the battery

terminals. Red pos. (+) lead to positive terminal and black

neg. (-) lead to negative battery terminal. Upon proper

connection, test alarm will sound. Press alarm reset to

silence. This indicates proper charger to battery connection.

CAUTION

Correct battery hook up is essential for

operation of the system. Use wing nuts supplied with battery

and eyelet connectors on battery wire leads. The positive

terminal is the larger stud, 3/8" diameter. The smaller stud,

5/16" diameter is the negative terminal. Apply grease to the

terminals to help prevent corrosion.

15. Connect the black lead from the pump to the negative (-)

battery terminal. Connect the white or red lead from the

pump to the white lead from the switch. This connection is

made at the fuse installed on the switch wire (see figure 3).

Connect the black lead from the switch to the positive (+)

battery terminal.

16. Connect the blue sensor wire to the sensor connector

(figure 3).

17. Close battery box and secure cover. Carpeted or

wood barrier between the battery case and the floor is

recommended.

18. Plug the control power cord into the 115V wall outlet. The

primary sump pump and the control box should be on

separate circuits.

19.

Reconnect power to primary sump pump.

20. Optional: A dongle may be used to input a name and number

into the charger for service information to the end user.

21. Optional: On the bottom of the charger there is a pair of

dry contacts to signal an auxiliary device of a low battery,

high water and reverse polarity alarm condition. This simple

2-wire connection is rated at a maximum of 24V AC/DC

and 0.5 amps. It can be used with an auto-dialer, alarm

or home security system. Read the auxiliary equipment's

documents for further instructions.

1. The preferred method of installation for backup pumps is

shown in figures 1 and 2. The installation kit includes the

necessary fittings and one check valve for installing with the

backup pump discharging into the primary pump outlet pipe.

An additional check valve is incorporated in the discharge

of the backup pump NOTE: Do not install in small spaces

where the charger will not be properly cooled.

2. Remove all parts from shipping carton and make sure all

parts are included. Refer to checklist on page 2.

3. Select location for battery and control charger. Control

charger must be within 6' of a 115V wall outlet and within 6'

of pump and basin. Connect to a separate circuit, different

than the primary pump.

4. If primary pump is installed, disconnect power. If the primary

pump is a column pump with adjustable float, and you are

installing per figure 2, check the “on” point and adjust to

approximately 7 ½" from bottom of pump (see figure 2). Mark

the discharge pipe 7" above the “on” point of the primary

column pump or 7" above the top of the primary submersible

pump.

5. If existing discharge pipe is metal or flexible tubing, it will

need to be replaced with SCH. 40 PVC piping. Use a male

adapter for connecting to the primary pump outlet.

6. Remove the discharge pipe and cut off at the mark determined

in step 4. Remove an additional 8" from the bottom portion.

7. Screw the discharge pipe into the primary pump outlet.

Tighten with strap wrench.

8. Assemble discharge fittings per figure 4. Note: Pump must

be glued into tee fitting on a 30° angle to avoid air locking

(see figure 4). Rotate pump while gluing until the line on

the discharge is facing up. Use a commercial grade of PVC

cleaner and solvent cement (not furnished with kit) on the

socket joints.

9. Install the pump and discharge assembly per figure 1 or 2.

10. Assemble the float assembly per figure 5.

11. Install the float switch assembly bracket above the outlet

tee using the clamp provided (see figures 1 and 2). Make

certain the clamp is tight on the pipe to avoid slippage. Use

electrical tape below the clamp to help prevent the clamp

from moving. Ensure that the “off” level of the float is 1"

min. above the discharge tee of the DC backup pump (see

figures 1 and 2). Position pumps in the sump and move

float up and down, making sure of free movement without

interference from any obstructions inside the sump or lid.

Very shallow sumps may require some adjustment to avoid

overfilling or backing up of water into the sump inlet. The

float switch can be moved on the discharge pipe or the

rubber stops can be adjusted as necessary. Cut extra float

rod length below lower float stop to prevent debris from

interfering with float operation.

Advertising
This manual is related to the following products: