Maintenance troubleshooting information, Carbon monoxide detectors – Star Water Systems FB12DCC (Flint & Walling) User Manual

Page 8

Advertising
background image

8

© Copyright 2013. All rights reserved.

NOTE: The purchase of an Aquanot

®

Battery will extend the Limited Warranty to three years from date of installation.

NOTE: Three-year limited warranty is valid only when a complete system is purchased and used as a backup to a primary dewatering

system. A complete system includes a Silent Sentry® and an Aquanot Battery.

MAINTENANCE

TROUBLESHOOTING INFORMATION

1. Inspect and test system for proper operations at least

every 3 months.*

(a) Red power on indicator light should be “on” indicating

AC power is on.

(b) Unplug primary pump and the control charger from

power supply.

(c) Fill sump with water to the “on” level for the DC pump.

Allow pump to run a few minutes.

(d) The alarm will sound approximately 3 seconds after

the pump starts to run.

(e) Push alarm reset switch. The alarm will go “off”.

(f) Pump will shut off after water level is lowered and the

float drops to the off position.

2. Plug the control charger and the primary pump into the

wall outlet.

(a) The primary pump will come on and lower the water to

the normal operating level and shut off.

(b) The “yellow” charging light should be on. The charger

is replacing the energy consumed during the test. The

“green” light will come on after the charger has replaced

the energy consumed during the test.

3. Battery should be agitated gently every 3 months.

CAUTION

Battery acid is dangerous. Take proper safety

precautions. Do not splash the acid. Add distilled water

to battery when necessary per battery manufacturer's

instructions.

* Wet cell batteries should be checked every month.

1. Charging and charged LED’s alternate frequently.

(a) This is normal.

2. DC Pump won’t run.

(a) Check 15 amp fuse in line from pump to switch (see

fig. 3). If fuse is blown, replace with 15 amp Littelfuse

type 3AG, series 311.

(b) Check for proper connections.

(c) Check all wire terminal points. Clean if required.

(d) Check for low battery. Service battery if required.

3. Pump runs but pumps very little or no water.

(a) Check for low battery. Battery will recharge if Red

power “on” light indicates power has been restored

and the float switch is in the off position.

(b) If immediate usage is required, remove and replace

dead battery with a full recharged battery.

(c) Due to varying conditions the pump may continue to

run on a low battery without sufficient power to remove

water. Pump will not stop running until battery is

completely discharged.

(d)

CAUTION

Weak batteries can be recharged but

may not store sufficient energy for full service. A weak

recharged battery can only be detected by reduced

pumping time or by checking each cell with a hydrometer.

If your emergency pump system is used frequently

the battery should be checked by a qualified battery

dealer.

4. Pump cycles too frequently.

(a) Check positions of rubber stops on float rod.

(b) Adjust upper rubber float stop as required. Recommended

for standard installation.

5. Float switch in “on” position. Pump won’t run.

(a) Remove pump. Check for obstruction in pump preventing

impeller from rotating.

6. Pump runs, but pumps water intermittently.

(a) Pump is air locking. Check flow of water incoming to

sump. If water is entering the sump at a high velocity

creating a turbulent condition, a mixture of air and water

may cause a complete or partial air lock and reduce or

stop the flow of water in the discharge pipe.

(b) Baffle the incoming stream of water to reduce turbulence.

Diverting water stream against wall of basin usually

corrects an air lock problem.

7. Water level stays high. DC Pump continues to run.

(a) Battery is low.

(b) If power has been restored and water in sump remains

high check primary pump. Service if required.

(c) After several hours the battery will be restored to full

charge.

8. Alarm sounds during battery recharge cycle.

(a) Push alarm reset (max. 3 times). If condition persists,

replace battery.

(b) To silence alarm if alarm will not reset, unplug the

charger from 115V wall outlet, then disconnect the black

lead from charger on negative (-) battery post. Check

battery. Replace if necessary. Reconnect and refer to

Installation (step 14).

Whether you have a Silent Sentry

®

Backup Pump System, or a competitive brand, all use batteries that give off

gaseous byproducts when charging. Some of these byproducts can produce a rotten egg odor. Also, some of these

byproducts can cause a CO detector to falsely activate. In order to help prevent false activation, we recommends

moving the battery as far apart from the CO detector as possible or, if necessary, vent the battery to the exterior. Flint &

Walling provides the previous statements only as guidelines to help prevent false activation of the CO detector. In no way are they

meant to supersede the instructions that accompany the detector nor do they supersede advice from the CO detector manufacturer.
If the audible alarm associated with your CO detector is activated, we recommend the following actions:
1) Take immediate action for personal safety as recommended in the CO detector literature.
2) Contact the appropriate agency to determine if the CO is being produced by your furnace, water heater, or any other device

which uses natural gas.

3) If you are certain that no CO is being produced, then a charging battery may be producing gaseous byproducts which are

causing the CO detector to activate. Contact the manufacturer and ask for recommendations as to what can be done to prevent

the alarm activation.

CARBON MONOxIDE DETECTORS

Advertising
This manual is related to the following products: