Van Air Systems D42-D84 User Manual

Page 6

Advertising
background image

PAGE 6

4.1 DAILY PROCEDURES

After every 8 hour period of operation, drain accumulated solution

from the bottom of dryer. Open manual drain valve and allow the

solution to discharge from the dryer, then close the manual drain
valve securely.

4.2 MONTHLY PROCEDURES

Check the level of the desiccant bed by looking into the sight window.

If the top of the desiccant bed is level with the sight window, the

desiccant bed must be replenished.

Check the operation of all equipment installed before and after the

dryer.

Check the afterfilter element condition. If the pressure differential

across the filter is high (6 to 9 PSID), replace the element.

Inspect the hatch cover for signs of corrosion and/or leaks. Replace

the cover and/or gasket if necessary.

4.3 REPLACING THE SIGHT WINDOWS

(P/N 26-0104)

WARNING

DEPRESSURIZE DRYER COMPLETELY BEFORE

REMOVING THE SIGHT WINDOW.

Using a pipe wrench, unthread the old sight window. Remove

all pipe sealant, rust or dirt from the coupling.

Apply a layer of pipe sealant to the threads of the new sight

window. DO NOT USE TEFLON TAPE. Tape may prevent

the sight window from threading into the coupling far enough.

4.4 DESICCANT SUPPORT GRID

If the grid becomes damaged, it can be replaced. The grid consists

of plastic grid pipes and steel top rings.

Should the grid require replacment, detailed instructions for

replacement will be provided with the new grid.

3.1 START UP PROCEDURES

Close the inlet isolation valve and open the bypass valve.

Open the outlet isolation valve SLOWLY and allow some air to bleed

through the drain valve; then close the drain valve. When the dryer

reaches normal operating pressure, SLOWLY turn the inlet valve to

full open position; then close the bypass valve.

If the vessel was installed without the bypass or isolation valves,

SLOWLY pressurize the air system. Allow some air to bleed through

the drain valve. Once the vessel starts to pressurize, the drain valve

can be closed.

Close the bypass valve. The dryer is now on stream.

CAUTION

Make sure that the dryer is not subjected to sudden flow

surges. Always open the valves slowly to permit gradual

equalization of pressure between the dryer and the air

supply lines.

3.2 OPERATING THE DRYER

The simple design of the single tower dryer allows for easy

operation. The dryer requires two procedures to ensure peak

performance.

On a new installation, continue to drain all downstream traps for

several days (or until no water is evident) after dryer is installed.

This period is required to dry out any accumulated water in the

compressed air system. Once the water is removed, the down-

stream traps should not need to be drained again.

3.2-B REFILLING THE DRYER WITH DESICCANT

During the VAN AIR drying process, the desiccant tablets dissolve

slowly. More tablets must be added to the supply when the top of

the bed drops to the sight window level (minimum level). Reference

FIGURE 5.

The desiccant consumption rate depends on several factors, such

as inlet temperature, flow, pressure and the type of desiccant being

used . With average conditions, the desiccant will usually need to

be added only two to three times per year when the dryer is

operating one shift per day. However, until the actual usage rate

is determined, check the bed level monthly.

Reference Section 4.5 for estimated consumption rates and

refilling instructions.

IMPORTANT

Use VAN AIR desiccant only. Filling dryer with any

other material will void the warranty.

WARNING

IF THE SIGHT WINDOWS ARE DAMAGED IN ANY WAY,

REPLACE THEM IMMEDIATELY WITH VAN AIR

PART NO. 26-0104 only. REFERENCE SECTION 4.3.

3.3 USING THE SIGHT WINDOWS

To check the level of the desiccant bed, look into one of the sight

windows. When the top of the desiccant bed is level with the sight

windows, the desiccant supply has dropped to the minimum level.

The bed must be replenished to raise the bed level to the maximum

level.

3.2-A DAILY DRAINING

The accumulated solution in the bottom of the dryer should be

drained at least once for every 8 hours of operation.

Depending upon actual operating conditions, the dryer may

require draining on a more frequent basis.

If an automatic ball valve type drain valve was installed on the

dryer, set the time cycle for every 4 to 8 hours. If a manual

drain valve was installed, it must be opened at least once every

4 to 8 hours to drain the dryer.

CAUTION

If the dryer is not drained regularly, it may become

flooded. Accumulated liquid may enter the air system and

cause damage to downstream equipment.

SECTION 3

OPERATION

SECTION 4

MAINTENANCE

Advertising