Quick programming, Activation, Emo-500 – AW Gear Meters EMO-500 User Manual

Page 15

Advertising
background image

EMO-500

Operation and Programming Manual

14


Figure 6: Quick Programming Display Screens

Quick Programming

Many programming variables such as KFR

or meter selection only require a "one time" setting; other

variables require some experimentation to find maximum efficiency settings. It is also desirable to allow
field personnel the limited ability to make some quick adjustments.

To accommodate these circumstances the EMO-500’s "Quick Programming" option allows you to jump
directly into some limited programming functions. These functions are noted in red on the keypad on
the top line of function keys F1 through F6, and the 0 and 1 keys (also see Figure 6). The keys and their
functions are:

F1 = Ideal Ratio

F2= Gate Time

F3 = Ratio Warning %

F4 = Ratio Alarm %

F5 = Decimal Point

F6 = Enter

0 = Sample Size

1 = Specific Gravity

Activation

To activate Quick Programming, connect the Scroll Line Input (Pin 2) and the “Common 1 – 5” (Pin 6) of
the 15-Pin connector on the back panel of the EMO-500 with a momentary contact switch. With this
connection established, push any one of the above keys.

This does not work if full programming is enabled.

A rate scaling factor.