No pe – HT instruments SIRIUS87 User Manual

Page 32

Advertising
background image

SIRIUS

87

EN - 30

 If the instrument detects that the earth

cable (green) is not connected, the
screen alongside is displayed for 5
seconds then the initial display is back.
Check the connections of PE conductor
under test.

RCD

~



>

1999




no

PE


THE PREVIOUS RESULT CANNOT BE SAVED.


 In the tests MAN x1, x2, x5 and AUTO

(during x1 and x5 tests), if the RCD
trips to separate the circuit within a time
not complying with the limits reported in
table, the instrument emits

a long

sound signal at the end of the test and
displays the values alongside.

RCD

~



 487

ms

N



30

m

A

1

V

x

1

MAN



t

U

L

=

50

V


 If the RCD trips within a time higher

than the instrument’s measuring limits,
the instrument emits

a long sound

signal at the end of the test and
displays the values alongside.

RCD

~



>

999

mS

N



30

m

A

2

V

x

1

MAN



t



U

L

=

50 V


The maximum duration depends on the test type:

Test type

General RCD

Selective RCD

MAN x1 test

999ms

999ms

MAN x2 test

200ms

250ms

MAN x5 test

50ms

160ms

“ ” test

300ms


SAVING:

The tests can be stored pressing the

SAVE key twice

(according to § 5.1).

RCD tripping time

ATTENTION: the
tripping time is
higher than the
standard limit.

RCD tripping
time:
> maximum
measuring time
(it depends on
type of test, see
following table)
.

Message
“no PE”: the
instrument does
not detect the
protection circuit.

SAVE

or RCD

or RCD

SAVE