If the instrument detects that the earth
cable (green) is not connected, the
screen alongside is displayed for 5
seconds then the initial display is back.
Check the connections of PE conductor
under test.
RCD
~
>
1999
no
PE
THE PREVIOUS RESULT CANNOT BE SAVED.
In the tests MAN x1, x2, x5 and AUTO
(during x1 and x5 tests), if the RCD
trips to separate the circuit within a time
not complying with the limits reported in
table, the instrument emits
a long
sound signal at the end of the test and
displays the values alongside.
RCD
~
487
ms
N
30
m
A
1
V
x
1
MAN
t
0°
U
L
=
50
V
If the RCD trips within a time higher
than the instrument’s measuring limits,
the instrument emits
a long sound
signal at the end of the test and
displays the values alongside.
RCD
~
>
999
mS
N
30
m
A
2
V
x
1
MAN
t
0°
U
L
=
50 V
The maximum duration depends on the test type:
Test type
General RCD
Selective RCD
MAN x1 test
999ms
999ms
MAN x2 test
200ms
250ms
MAN x5 test
50ms
160ms
“ ” test
300ms
SAVING:
The tests can be stored pressing the
SAVE key twice
(according to § 5.1).
RCD tripping time
ATTENTION: the
tripping time is
higher than the
standard limit.
RCD tripping
time:
> maximum
measuring time
(it depends on
type of test, see
following table).