INOR IPAQ-4L GB User Manual

Universal high-isolation 4-wire transmitter

Advertising
background image

MEASURE OF SUCCESS

USER INSTRUCTIONS

www.inor.com, www.inor.se

The manual must be read prior to adjustment

and/or installation. All information subject to

change without notice.

The transmitter is configured from a standard IBM compatible PC

by using the IPRO software (version 4.1 or later). IPRO 4.1 is com-

patible with Windows 98SE, Windows NT Workstation 4.0, Windows

2000 and Windows XP. When the transmitter is reconfigurated by a

PC no recalibration is needed.

Connect the IPRO communication cable between the serial port of

a PC (with IPRO software installed) and the PC connection port on

IPAQ-4L.

The IPAQ-4L must be powered, when you configure the

transmitter.

If IPRO (the IPAQ software) isn’t installed in your PC, install the

software (follow the instructions in ”IPRO”). Configuration from

PC is “on-line”, that is, the transmitter can be installed in the process

with input connected during configuration. The output is frozen while

transmission from PC to IPAQ take place. When transfer is done the

transmitter uses the new parameters.

NOTE: The label on the transmitter indicate allowed power supply

to the transmitter. By connecting false power supply the

transmitter may be damaged.

INTRODUCTION

IPAQ-4L is a fully universal and programmable 4-wire (separately

powered) transmitter. The high isolation provides safe and problem

free measurements. Offering both current and voltage output,

IPAQ-4L meets any process requirements. Designed for wall and

DIN-rail mounting.

IPAQ-4L is intended to be used in industrial environment.

DIMENSIONS

Universal

High-Isolation

4-wire Transmitter

CONFIGURATION

SWEDEN

GERMANY

USA

FINLAND

Since IPAQ-4L

is a precision instrument it´s recommended to check

the calibration once a year. Use equipment with an

inaccuracy of at least 5 times better than the checked one, e.g. if you

are checking a transmitter with an inaccuracy of 0.1% use instrument

with an inaccuracy of maximum 0.02%.

You can either perform a full recalibration of the transmitters stored

calibration parameters (Basic Calibration) or make a System

Error Correction (recommended). In each case use the IPRO software

and follow the instructions on the screen. When performing a System

Error Correction, please note that this is only a compensation for

errors at the measuring range in use.

CALIBRATION

86BIQ00007 2012-10

mm/inches

This pr

oduct should not be mix

ed wi

th other kind of scr

ap

, after usage. It should be handled as an electr

onic/electric device.

PC connection

ADDRESS 7 Dearborn Road,

Peabody, MA 01960

USA

PHONE

+1-978-826 6900

FAX

+1-978-535 3882

E-MAIL

[email protected]

ADDRESS PO Box 9125

SE-200 39 Malmö

Sweden

PHONE

+46-40-31 25 60

FAX

+46-40-31 25 70

E-MAIL

[email protected]

ADDRESS Am Bocksborn 5

D-63571 Gelnhausen

Germany

PHONE

+49-6051 14807

FAX

+49-6051 14806

E-MAIL

[email protected]

ADDRESS Unikkotie 13

FI-01300 Vantaa

Finland

PHONE

+358-10-421 7900

FAX

+358-10-421 7901

E-MAIL

[email protected]

INOR Process AB

INOR Transmitter GmbH

INOR Transmitter Oy

KROHNE Temperature

Division INOR

Advertising