USER INSTRUCTIONS English

Loop Powered Isolator























www.inor.com




Read these instructions before
using the product and
retain for future information.








1. Before Startup

The isolator should only be installed and put into
operation by qualified staff. The staff must have
studied the warnings in these operating instructions
thoroughly.

The isolator should only be installed and put into
operation by qualified staff. The staff must have
studied the warnings in these operating instructions
thoroughly.

The isolator may not be put into operation if the
housing is open.

The isolator may not be put into operation if the
housing is open.

In applications with high operating voltages
sufficient distance and isolation as well as shock
protection must be ensured.

In applications with high operating voltages
sufficient distance and isolation as well as shock
protection must be ensured.

Safe and trouble-free operation of this device can
only be guaranteed if transport, storage and
installation are carried out correctly and operation
an maintenance are carried out with care.

Safe and trouble-free operation of this device can
only be guaranteed if transport, storage and
installation are carried out correctly and operation
an maintenance are carried out with care.



Appropriate safety measures against electrostatic
discharge (ESD) should be taken during connection and
assembly on the isolator.

Appropriate safety measures against electrostatic
discharge (ESD) should be taken during connection and
assembly on the isolator.

2. Short description

2. Short description
The loop powered isolator is used for electrical isolation and
processing of 0(4) - 20 mA standard signals.

The loop powered isolator is used for electrical isolation and
processing of 0(4) - 20 mA standard signals.

The galvanic isolation guarantees reliable decoupling of the sensor
circuit from the processing circuit and prevents linked measurement
circuits from influencing each other.

The galvanic isolation guarantees reliable decoupling of the sensor
circuit from the processing circuit and prevents linked measurement
circuits from influencing each other.



3. Functioning

3. Functioning
The input signal is modulated and then electrically decoupled using
a transformer. The isolated signal is then made available at the
output, demodulated and filtered.

The input signal is modulated and then electrically decoupled using
a transformer. The isolated signal is then made available at the
output, demodulated and filtered.

When using loop-powered Isolators, ensure that the current-driving
voltage of the power source U

S

is sufficient for driving the maximum

current of 20 mA over the isolator with voltage drop of U

drop

= 2 V

and the load Rl

oad

.

When using loop-powered Isolators, ensure that the current-driving
voltage of the power source U

S

is sufficient for driving the maximum

current of 20 mA over the isolator with voltage drop of U

drop

= 2 V

and the load Rl

oad

.


U

S

U

IN

= 2 V + 20 mA x R

load

U

S

U

IN

= 2 V + 20 mA x R

load



Optional use:

U

T

= U

S

- 2 V - 20 mA x R



4. Equipment
A screwdriver with a width of 2.5 mm is required connect the wires
to the screw clamp terminals.


5. Mounting, electrical connection
The isolation transmitter is mounted on standard 35 mm DIN rail.

Terminal assignments

Channel 1

Channel 2

1 Input

+

3 Input

+

2 Input

-

4 Input

-

5 Output +

7 Output +

6 Output -

8 Output -




6. Order information

Product

Input / Output

Part No.

IsoPAQ-11L

1-channel, 0(4) - 20 mA

70ISL11001

IsoPAQ-12L

2-channel, 0(4) - 20 mA

70ISL12001


7. Technical Data

Input

Input signal

0(4) - 20 mA / max. 30 V

Operating current

< 20

µA

Voltage drop

< 2 V

Overload

≤ 100 mA, ≤ 30 V

Output

Output signal

0(4) - 20 mA / max. 28 V

Response time
(10 to 90 % of end value)

2 ms @ 250

Ω load / 6 ms 750 Ω load

Ripple

< 20 mV

rms

General data

Transmission error

± 0.1 % of end value

Load error

± 0.03 % of measured value / 100 Ω load

Temperature coefficient

1)

± 0.0015 %/K of measured value / 100 Ω load

Test voltage

1.5 kV, 50 Hz

Between all circuits

Ambient temperature


Operation
Transport
and storage

- 20 °C to + 70 °C (-4 to +158 °F)
- 35 °C to + 85 °C (-31 to +185 °F)

EMC

2)

EN 61326 -1

Construction

12,5 mm (0.5’’) housing, protection type: IP 20

Connection

≤ 2.5 mm

2

, AWG 14

Weight

Approx. 100 g

1) Average TC in specified operating temperature range
2) Minor deviations possible during interference





8. Block diagram


9. Dimensions







LIMITED WARRANTY


INOR Process AB, or any other affiliated company within the
Inor Group (hereinafter jointly referred to as ”Inor”), hereby
warrants that the Product will be free from defects in materials
or workmanship for a period of five (5) years from the date of
delivery (”Limited Warranty”). This Limited Warranty is limited
to repair or replacement at Inor’s option and is effective only for
the first end-user of the Product. Upon receipt of a warranty
claim, Inor shall respond within a reasonable time period as to
its decision concerning:

1. Whether Inor acknowledges its responsibility for any

asserted defect in materials or workmanship; and, if so,

2. the appropriate cause of action to be taken (i.e. whether

a defective product should be replaced or repaired by
Inor).


This Limited Warranty applies only if the Product:

1. is installed according to the instructions furnished by

Inor;

2. is connected to a proper power supply;
3. is not misused or abused; and
4. there is no evidence of tampering, mishandling, neglect,

accidental damage, modification or repair without the
approval of Inor or damage done to the Product by
anyone other than Inor.


This Limited Warranty is provided by Inor and contains the only
express warranty provided.

INOR SPECIFICALLY DISCLAIMS ANY EXPRESS WARRANTY NOT
PROVIDED HEREIN AND ANY IMPLIED WARRANTY, GUARANTEE OR
REPRESENTATION AS TO SUITABILITY FOR ANY PARTICULAR
PURPOSE, PERFORMANCE, QUALITY AND ABSENCE OF ANY
HIDDEN DEFECTS, AND ANY REMEDY FOR BREACH OF CONTRACT,
WHICH BUT FOR THIS PROVISION, MIGHT ARISE BY IMPLICATION,
OPERATION OF LAW, CUSTOM OF TRADE OR COURSE OF DEALING,
INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE. EXCEPT AS PROVIDED
HEREIN, INOR FURTHER DISCLAIMS ANY RESPONSIBILITY FOR
LOSSES, EXPENSES, INCONVENIENCES, SPECIAL, DIRECT,
SECONDARY OR CONSEQUENTIAL DAMAGES ARISING FROM
OWNERSHIP OR USE OF THE PRODUCT.


Products that are covered by the Limited Warranty will either
be repaired or replaced at the option of Inor. Customer pays
freight to Inor, and Inor will pay the return freight by post or
other “normal” way of transport. If any other type of return
freight is requested, customer pays the whole return cost.