5 light tower cable wiring overview, Cable wire colors, 6 installation procedure – In-Situ Light Tower Alarm Kit for the Con TROLL PRO System User Manual

Page 3: Light tower cable wiring overview, Installation procedure

Advertising
background image

800-446-7488

3

www.in-situ.com

Light Tower Cable Wiring Overview

The light tower is not polarity sensitive and can be wired one of two ways:

1. The common wire connected to POWER and the other wires switched by relay to

GND.

2. The common wire connected to GND and the other wires switched by relay to

POWER.

All of the examples provided in this document use the first method. If you want to install
additional accessories with the light tower, the second method might be used. Consult
a qualified technician for additional configurations.

Cable Wire Colors

Wire Color

Function

Blue

Common

Black

Green Light

Brown

Yellow Light

White

Red Light

Gray

Audible Indicator

Installation Procedure

Refer to the Con TROLL PRO Installation Manual as needed.

1. Install the light tower using the supplied bracket, making sure the cable reaches the

Con TROLL PRO without strain.

2. Disconnect power from the Con TROLL PRO.

3. Loosen the four screws on the front panel and open the front panel.

4. If necessary, remove a wiring port plug on the Con TROLL PRO and replace it with

a dome connector.

5. Insert the light tower cable and pull it inside the enclosure far enough for the wires to

reach the terminal block without strain.

6. Tighten the dome connector to seal the enclosure and to provide strain relief for the

cable.

7. Wire the light tower cable according to the appropriate diagram for the intended

application. See pages 4 through 7.

8. Trim the exposed ends of any unused light tower wires.

9. Secure unused light tower wires to the light tower cable with zip ties.

Advertising