10. Close the front panel and tighten the four front panel screws.

11. Apply power to the Con TROLL PRO.

12. Program the relay outputs to match the selected configuration.

Configuring a Single-Parameter Light Alarm

In this scenario, the Con TROLL PRO monitors a tank using an RDO

®

PRO Probe. The

Con TROLL PRO turns on an aerator when the dissolved oxygen (DO) concentration
falls below 4 mg/L. The light tower shows green when the DO is above 4 mg/L (aerator
off), and yellow when the DO is below 4 mg/L (aerator on).

The RDO PRO Probe is wired as Probe A. Relay 1 is used to implement the control
and display function.