INSTALLATION
1
7
OPTISONIC 6300
www.krohne.com
07/2009 - 7.30959.24.00 - QS OPTISONIC 6300 R04 en
1.7.1 Inlet, outlet and recommended mounting area
1.7.2 Long horizontal pipes
• Install on slightly ascending pipe section.
• If not possible, ensure adequate velocity to prevent air, gas or vapor from collecting in upper
part.
• In partially filled pipes, the clamp-on flowmeter will report incorrect flow rates, or not
measure.
Figure 1-3: Inlet, outlet and recommended mounting area
1 Min. 10 DN
2 Min. 5 DN
3 OK, 120°
CAUTION!
Especially for XT (eXtended Temperature) versions:
•
Always install the sensor at a non-insulated part of the pipe. Remove any insulation if
necessary!
•
Bend radius of cable plus connection box needs 10 cm / 4" additional non insulated pipe
section.
•
Always wear protections gloves.
Figure 1-4: Long horizontal pipes