Installation, 3 installation requirements for concrete roofs – KROHNE OPTIFLEX 2200 C_F Quickstart EN User Manual

Page 12

Advertising
background image

2

INSTALLATION

12

OPTIFLEX 2200 C/F

www.krohne.com

08/2013 - 4000622103 - QS OPTIFLEX 2200 R03 en

For double cable and double rod probes:

For coaxial probes:

If your device has a coaxial probe, you can ignore these installation recommendations.

2.7.3 Installation requirements for concrete roofs

Figure 2-12: Recommended nozzle dimensions for double rod and double cable probes

d ≥ 50 mm / 2¨, where d is the diameter of the tank nozzle

CAUTION!
Install coaxial probes in clean liquids that are not too viscous.

Figure 2-13: Installation on a concrete roof

1 The diameter, d, of the hole must be greater than the thickness, t, of the concrete.
2 If the thickness, t, of the concrete is greater than the diameter, d, of the hole, install the device in a recess.