Electrical connections, 6 networks, 1 general information – KROHNE OPTIFLEX 2200 C_F Quickstart EN User Manual
Page 41: 2 point-to-point networks

ELECTRICAL CONNECTIONS
3
41
OPTIFLEX 2200 C/F
www.krohne.com
08/2013 - 4000622103 - QS OPTIFLEX 2200 R03 en
3.6 Networks
3.6.1 General information
The device uses the HART
®
communication protocol. This protocol agrees with the HART
®
Communication Foundation standard. The device can be connected point-to-point. It can also
operate in a multi-drop network of up to 15 devices.
The device output is factory-set to communicate point-to-point. To change the communication
mode from point-to-point
point-to-point
point-to-point
point-to-point to multi-drop
multi-drop
multi-drop
multi-drop, refer to "Network configuration" in the handbook.
3.6.2 Point-to-point networks
Figure 3-11: Point-to-point connection (non-Ex)
1 Address of the device (0 for a point-to-point connection)
2 4...20 mA + HART
®
3 Resistor for HART
®
communication
4 Power supply
5 HART
®
modem
6 HART
®
communication device