To damp process-dependent measured value fluctua-
tions, you have to set an integration time of 0 … 999 s in
this menu item.
Damping
In this menu item you select the linearization curve:
l
linear
l
Cylindrical tank
l
Spherical tank
l
User programmable
User programmable means: Switching on a linearization
curve programmed via PC and PACTware™
The linearization curve relates height and volume. It
takes the vessel geometry for the measured value
display and the current output into account.
Lineari-
zation
curve
linear
In the menu item "Sensor TAG" you edit a 12-digit
measurement loop character. The character set com-
prises:
l
Letters from A … Z
l
Numbers from 0 … 9
l
Special characters +, -, /, –
Sensor
TAG
Sensor
Min. and max. measured values are saved in the sensor.
The values are displayed in the menu item "Peak
values".
l
Min. and max. distance in m(d)
l
Min. and max. temperature
Damping
Linearization curve
Edit senor TAG
Peak values
Indicating/adjustment module for OPTISOUND sensors
15
Set up
30603
-EN