ELECTRICAL CONNECTIONS

4

39

IFC 050

www.krohne.com

08/2013 - 4002184002 - MA IFC 050 R02 en

Pulse/frequency output passive

• U

ext

≤ 32 VDC

• f

max

in the operating menu set to f

max

≤ 100 Hz:

I ≤ 100 mA
R

L

≤ 47 kΩ

closed:
U

0

≤ 0.2 V at I = 10 mA

U

0

≤ 2 V at I = 100 mA

open:
I ≤ 0.05 mA at U

ext

= 32 V

• f

max

in operating menu set to 100 Hz < f

max

≤ 10 kHz:

(over range up to f

max

≤ 12 kHz)

I ≤ 20 mA
R

L

≤ 10 kΩ for f ≤ 1 kHz

R

L

≤ 1 kΩ for f ≤ 10 kHz

closed:
U

0

≤ 1.5 V at I = 1 mA

U

0

≤ 2.5 V at I = 10 mA

U

0

≤ 5 V at I = 20 mA

open:
I ≤ 0.05 mA at U

ext

= 32 V

Use shielded cables!

• The minimum load impedance R

L, min

is calculated as follows:

R

L, min

= (U

ext

- U

0

) / I

max

• Can also be set as status output; for the electrical connection refer to status output

connection diagram.

INFORMATION!

•

For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).

•

Shielding takes place at the electrical connection (S) of the output terminal block.

INFORMATION!

•

Independent of connection polarity.

•

The output is open if the signal converter is not powered.