OPERATION
6
59
IFC 050
www.krohne.com
08/2013 - 4002184002 - MA IFC 050 R02 en
No.
Function
Settings / descriptions
C4 I/O HART
The dynamic variables are fixed to the following values:
PV: flow (volume flow or mass flow, depending on the selection of "measurement" in Fct. C1.1.4)
SV: counter 1
TV: counter 2
4V: operating time
C4.1
HART
HART
®
communication is activated or deactivated.
Select:
on (HART
®
is activated; default setting) /
off (HART
®
is disabled)
C4.2
address
Setting the address for multi-drop operation.
If "address 0" is selected, the current output is in normal operation. For all
other addresses, the current at the output is set to the 0% value.
C4.3
message
Input of individual text.
C4.4
description
Input of individual text.
C4.5
HART units
Unit change of dynamic variables in the display.
Select:
break (cancels copying process) /
display - HART (copies the settings for the display units to the settings for
the dynamic variables) /
load defaults (HART
®
dynamic variables are reset to defaults)