KROHNE OPTIMASS with MFC 300 EN User Manual

Page 114

Advertising
background image

114

Ref

Display

Description & Settings

C5 I/O HART

C5.1

PV is

Displays the HART PV. The PV is always as per the HART current out-
put

C5.2

SV is

Sets the HART variables SV, TV and 4V (QV). List depends on actual
configuration.

•

Volume flow rate

•

Mass flow rate

•

Temperature.

•

Density

•

Diagnosis1

•

Diagnosis2

•

Diagnosis3

•

Concentration 1

•

Concentration2

•

Conc Flow1

•

Conc Flow2

•

Counter 1

•

Counter 2

•

Counter 3

•

Operating hours

•

Flow Speed

C5.3

TV is

C5.4

4V is

C5.5

HART Units

Copies the display units to the HART interface:

Continue to copy?

Select:

Break - aborts function
Display HART- copies unit setting from display to those of the
HART dynamic variables
Load Defaults - sets HART dynamic units to defaults

C6 Device

C 6.1

Device Info

C 6.1.1

Tag

Measuring point identifier (Tag No.), also applies to HART® address
& also appears in the display header (up to 8 places)

C 6.1.2

C number

Electronic unit-No. (see signal converter nameplate) / unalterable

C 6.1.3

Device serial no.

Serial No. of the system / unalterable

C 6.1.4

BE serial no.

Serial No. of the complete electronic unit / unalterable

C 6.1.5

SW.REV. MS

Displays the Serial No, Software No and calibration date of the circuit
board

C 6.1.6

Electronics Revision ER

C.6.2

Display

C.6.2.1

Language

Select:

•

English

•

Deutsch

•

Français

•

Dansk

•

Polski

•

Portugues

•

Nederlands

•

Espanôl

C 6.2.2

Contrast

Setting range: -9…0…+9

C 6.2.3

Default meas. page

Select:

•

1st meas. page

•

2nd meas. page

•

None

•

status page

•

graphic page

C.6.2.5

SW. Rev. MS

Displays the Serial No, Software No, and calibration date of the cir-
cuit board display

C 6.3

1st meas. page 1

All functions and settings for the two pages are identical!
In the following descriptions “z“ characterizes the m.v. page:
page 1 = C 5.3

page 2 = C 5.4

C.6.4

2nd meas. page 2

C 6.z. 1

Function

•

one line

•

two lines

•

three lines

C 6.z. 2

Measurement 1

st

line

•

Volume flow rate

•

Mass flow rate

•

Temperature

•

Density

•

Diagnosis 1

•

Diagnosis 2

•

Diagnosis 3

•

Concentration 1

•

Concentration 2

•

Conc Flow 1

•

Conc Flow 2

•

Flow Speed