Figure 18, Contact the factory with questions about your, Figure 20 – Precision Control Systems 3629C User Manual

Page 17: Command connections (continued)

Advertising
background image

MODEL 3629C

13

04/10/2007

COMMAND CONNECTIONS (Continued)

Note: to insure proper operation,

isolation of the feedback source may

be required. Contact the factory for

further information.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

D.C. Feedback signal

Positive

Common

0 TO 5 Vdc

Input Impedance = 200K

IFB
EFB

P6

Determine that

jumper P6 is in

the EXTERNAL

FEEDBACK

position

Figure 18. External voltage feedback.

*On SP56 unit feedback is 0 to 10 Vdc and input impedance is 400K

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

RELAY CONTACTS

CHANGE STATE IF

AN SCR FAILS IN THE

SHORTED MODE

TO EXTERNAL

CIRCUIT AS

DESIRED

SHORTED

SCR

RELAY

Figure 19. Shorted SCR relay connections.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

MOMENTARY CLOSURE RESETS THE CONTROLLER.

(TEMPORARY REMOVAL OF POWER ALSO

RESETS THE CONTROLLER)

TERMINALS # 9 & 10 MAY BE WIRED TO A

REMOTE SWITCH FOR ON/OFF CONTROL.

RELAY CONTACTS CHANGE STATE

WHEN AN OVERCURRENT

CONDITION OCCURS

TO EXTERNAL

CIRCUIT AS

DESIRED

OVER CURRENT TRIP

RESET SWITCH

OVER

CURRENT

RELAY

Figure 20. Over current relay and reset switch connections.

Advertising