SPECIFICATIONS (Continued)

SCR Surge Current:

Peak 1 cycle surge current is:

50 Amp rating - 1,750 A Surge

80 Amp rating - 1,750 A Surge

120 Amp rating - 1,900 A Surge

160 Amp rating - 4,000 A Surge

200 Amp rating - 5,200 A Surge

250 Amp rating - 5,200 A Surge

300 Amp rating - 7,000 A Surge

380 Amp rating - 10,000 A Surge

425 Amp rating - 13,000 A Surge

500 Amp rating - 10,000 A Surge

600 Amp rating - 13,000 A Surge

750 Amp rating - 20,000 A Surge

1000 Amp rating - 26,000 A Surge

SCR I

2

T Rating:

50 Amp rating - 15,000 A

2

S

80 Amp rating - 15,000 A

2

S

120 Amp rating - 18,000 A

2

S

160 Amp rating - 80,000 A

2

S

200 Amp rating - 135,000 A

2

S

250 Amp rating - 135,000 A

2

S

300 Amp rating - 245,000 A

2

S

380 Amp rating - 500,000 A

2

S

425 Amp rating - 845,000 A

2

S

500 Amp rating - 500,000 A

2

S

600 Amp rating - 845,000 A

2

S

750 Amp rating - 1,670,000 A

2

S

1000 Amp rating - 2,815,000 A

2

S

SCR Voltage Rating:

50-750 Amp Frames: Peak forward and reverse voltage rating 1600V.

1000 Amp Frame:

Peak forward and reverse voltage rating 1800V.

SCR DV/DT Rating:

200 volts/usec minimum.

Loads:

Resistive, Variable resistance, Inductive, Capacitive, Transformer or Lamps.

Slew Rate:

200 milli-seconds. (Slew rate is the time required for the load voltage to change 63%

of the value represented by the command signal. The current limit action will change

the slew rate if the load current is greater than the current rating of the SCRs.

Frame Size:

The "(Amps)A" term within the model number specifies the maximum continuous

RMS current rating at the maximum operating ambient temperature of 55°C.