Specifications – Precision Control Systems 3629C User Manual

Page 7

Advertising
background image

MODEL 3629C

3

04/10/2007

SPECIFICATIONS

The following specifications apply over an ambient temperature range of 0 to 55°C and a supply voltage of 85% to 110%

of the nominal supply voltage rating.

Control Mode:

Three-phase in line, Three-phase inside delta, 4-wire wye or DC. 6 SCR, phase

angle control of the RMS or average load voltage. External feedback is available.

See

Power Connections

section.

Command Signal:

Input signal

Input Impedance:

0-5Vdc

200K ohms

0-10Vdc

200K ohms

Potentiometer

200K ohms

4/20mA

300 ohms

A 1K to 20K potentiometer is excited by 5Vdc, supplied by the circuit. Other input

signals may be available. Check with factory for special applications.

Control Range:

0 to 98% of line voltage.

Linearity:

Output will be linear within 2% of span over entire range of control.

Current Limit Range:

Adjustable from 20% to 125% of frame current as specified in the "(Amps)A" term

within the model number. If no IL term is specified when ordering, then current limit

is factory set to 105% of frame current rating.

Over Current Trip Range:

Adjustable from 30% to 300% of frame current as specified in the "(Amps)A" term

within the model number. If no OCT term is specified when ordering, then over

current trip is factory set to 175% of frame current rating.

Zero and Span Adjustments:

Multi-turn potentiometers allow zero and span adjustments of ±25% of span.

Dissipation:

Approximately 1.5 watts per amp of current per phase dissipated by the controller.

Supply Voltage:

208, 240, 380, 415, 480, or 575Vac, 3 phase, @ 50/60 Hertz. Other operating

voltages may be available by special order.

Environment:

Operating temperature 0 to 55°C (32 to 132°F).

Storage temperature: -40 to 85°C (-40 to 176°F).

Humidity: 0 to 95%, non-condensing.

Electrical Isolation:

Heat sink to supply

Load voltage on units rated 50 to 160 Amps:

2500 volts peak.

Command signal to supply and load voltage:

2500 volts peak.

Status Indicators:

LINE OK: Indicates power on all three phases and phase lock capture OK.

COMMAND: The intensity of this LED is proportional to the command signal.

LINE A, LINE B, LINE C: The intensity of these three LEDs is proportional to the

current in each leg.

SHORTED SCR: Indicates when an SCR has failed in the shorted mode.

OVER CURRENT: Indicates excessive current has occurred.

CURRENT LIMIT: Indicates when unit is in current limit mode.

Ready Signal:

An open drain Field Effect Transistor provides a signal which may be used to control

an LED, a relay or a logic level shift. This signal will remain high if conditions exist

within the controller that prevent the controller from providing a controlled output.

(See

Figure 14

).

Cooling:

Convection cooling on 50 amp unit.

Forced air fan cooling on all other models.