POWER CONNECTIONS (Continued)

FUSES

LINE 1

LINE 2

LINE 3

LOAD 1

LOAD 2

LOAD 3

TO

3 PHASE SUPP

LY

A

B

C

4 WIRE WYE LOAD

DELTA - 4 WIRE

WYE XFRMR

X
X

1 2

C

LO

S

E

D

Mode Switch

See Adjustments

Section

Note: It is recommended that the load and controller be protected by 3 class

"T" or "Semiconductor” fuses. Choose a fuse size approximately 120 to

125% of the current rating of the controller.

DELTA-WYE TRANSFORMER - With WYE load

Using a Delta primary to a 3 wire Wye secondary transformer into a wye load with an SCR

controller is not recommended. If the load across any two legs would happen to open, the

high voltages induced across the primary would almost certainly cause the SCR's to fail.

Using a fourth wire, to connect the junction of the secondary Wye to the junction of the Wye

load, would eliminate this problem.

See Replacement Parts sections.

Figure 27. In-line connections to delta-wye transformer coupled 4 wire wye load.

X
X

1 2

C

LO

S

E

D

Mode Switch

DELTA-WYE TRANSFORMER - With DELTA load

Applying a Delta load to the Wye secondary would be less likely to create the same problem,

as two loads would have to open to induce high voltages across the primary.

DE

LT

A

LOA

D

DELTA WIRE

WYE XFRMR

FUSES

LINE 1

LINE 2

LINE 3

LOAD 1

LOAD 2

LOAD 3

TO

3 PHASE SUPP

LY

A

B

C

See Adjustments

Section

Figure 28. In-line connections to a delta-wye transformer couple delta load.