MODEL NUMBER IDENTIFICATION

3629C-(FB)-(VOLTS)-(AMPS)-CS-IL(Amps)-(SC)-(OCT)-(SP-##)

Basic Model Number

Specifies Type of

Feedback

V specifies RMS voltage feedback.

(Desired for heating applications.)

A specifies Average voltage feedback.

(Desired in some DC applications.)

E specifies external feedback.

Specifies Supply Voltage.

Typical choices are:

208, 240,

380, 415, 480 or 575 Volts AC

Other voltages may be available,

call factory for details.

Specifies: Current Rating of the Controller.

Frame sizes are:

50, 80, 120, 160, 200, 250,

300, 380, 425, 500, 600 or 750 Amps

An unlisted

1000 Amp controller is available.

Specifies

Command Signal.

0-5Vdc or Potentiometer input are standard.

0-10 Vdc can be used after placing a jumper

on the circuit board.

Non-standard as well as mA input commands may be requested

at time of order.

If a potentiometer is used, 1K ohm is recommended for greater linearity,

up to 20K ohm is permissible.

Specifies

Current Limit.

Adjustable: Useable range of 20 to 125% of frame rating.

If not specified, current limit will be factory set to 105%

of specified frame current.

(Optional) Specifies

Special Calibration.

Contact factory for details.

(Optional) Specifies

Over Current Trip setting.

(If not specified, O.C.T. will be set to 175% at factory.)

(Optional) Specifies

Special Product

Contact factory with questions.

Examples:

3629C-V-480V-200A-4/20mA

This model number specifies a three-phase, 6 SCR, Phase-Angle controller, with true RMS voltage feedback, for 480

Volt operation at 200 Amps maximum and is factory modified to accept a 4/20mA command signal.

3629C-A-240V-160A-0/5V

This model number specifies a three-phase, 6 SCR, Phase-Angle controller, with average voltage feedback, for 240

Volt operation at 160 Amps maximum and accepts a 0 to 5Vdc command signal.