2 sensitivity ranges, Table 2: sensitivity range levels – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual

Page 20

Advertising
background image

SharpEye

TM

IR3 Flame Detector User Guide

8

Performance Considerations

1.5.1.2 Sensitivity Ranges

The detector has four user-selectable sensitivity ranges. For each range
there are two response levels.

WARNING (Pre-alarm)

ALARM

The detection distance, for the WARNING level, is approximately 10% higher
than the ALARM distance.

Alarm response times for a standard fire at a specified range are shown
Table 2.

Table 2: Sensitivity Range Levels

Level

Response Time (sec)

Sensitivity Range- ft. (m)

1

3

50 (15)

2 Default

5

100 (30)

3

8

150 (45)

4

10

215 (65)

For some typical ambient conditions the Zeta parameter as defined in NFPA
72 for the detector is 0.005 (1/meter).

Note: Zeta parameters may vary significantly with changes in temperature,
air pressure, humidity, visibility conditions, and so on.

Advertising