4 function set-up, Function set-up, Table 17: functions – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual

Page 43

Advertising
background image

TM 40/40I, Rev (6) July 2013

Configuring your Detector

31

2.8.4 Function Set-up

You can select the desired functions as detailed in Table 17.

Table 17: Functions

Function

Setting

Alarm Latch

Yes: Enable Alarm latching.

No: Disable Alarm latching (default).

Auxiliary Relay**

Yes: Activate Auxiliary Relay at Warning level.

No: Activate Auxiliary Relay at Alarm level

(default).

Automatic BIT

Yes: Perform Automatic & Manual Bit (default).

No: Perform Manual Bit only.

Alarm BIT

Yes: Successful Manual Bit activates the Alarm
Relay for approximately 3 seconds (default).

No: Successful Manual Bit does not activate the

Alarm Relay.

Auxiliary BIT**

Yes: Successful Manual Bit activates the
Auxiliary Relay for approximately 3 seconds
(default).

No: Successful Manual Bit does not activate the

Auxiliary Relay.

EOL**

Yes: Auxiliary Relay is used as End of Line.

No: Auxiliary Relay operates in accordance with

Function 2 and 5 (default).

Note: ** only available in Model 40/40I-4XXXX and 5XXXX