SIL-2 Features

In this appendix…

40/40I Flame Detector

page 65

E.1

40/40I Flame Detector

This appendix details the special conditions to comply with the requirements
of EN 61508 for SIL 2.

The 40/40I Flame Detector can only be used in low or high demand mode
applications, see IEC 61508.4, Chapter 3.5.12.

E.1.1 Safety Relevant Parameters

Perform the following functional checks of the detector:

Alternative 1: Functional check of the detector every 180 days:

HFT: 0

PFD: 3.0 x 10 -4 (≈ 3% of SIL-2) if only Alarm Relay is used for

alerting.

PFD: 3.2 x 10 -4 (≈ 3.2% of SIL-2) if 0-20mA – interface is used as

alarm.

PFH: 1.5 x 10 –7 1/h (≈ 14.9% of SIL-2) for 0-20mA application.

SFF: 95% fulfills the conditions of EN 61508 for SIL2

Alternative 2: Functional check of the detector every 365 days:

HFT: 0

PFD: 4.5 x 10 -4 (≈ 4.5% of SIL-2) if only Alarm Relay is used for

alerting.

PFD: 4.9 x 10 -4 (≈ 4.9% of SIL-2) if 0-20mA – interface is used

signal current as alarm.

PFH: 1.5 x 10 –7 1/h (≈ 14.9% of SIL-2) for 0-20mA application.

SFF: 95% fulfills the conditions of EN 61508 for SIL2

E.1.2 Guidelines for Configuring, Installing, Operating and

Service

The alert conditions according to SIL 2 can be implemented by an:

Alert signal via 20mA current loop

or

Alert signal via alarm relay and the fault relay