D.1.1, Unpacking, D.1.2 – Spectrex 40/40I Triple IR (IR3) Flame Detector User Manual

Page 70: Operating instructions, Figure 16: 40/40i ir3 detector target point, D.1.1 unpacking, D.1.2 operating instructions

Advertising
background image

SharpEye

TM

IR3 Flame Detector User Guide

58

Long Range IR3 Fire Simulator

D.1.1 Unpacking

Verify that you have received the following contents:

Delivery form

Fire Simulator with integral batteries

Battery charger

Optional Beam Collimator

Storage case

D.1.2 Operating Instructions

Warning: Do not open the Fire Simulator to charge the batteries or for any
other reason in a hazardous area.

Caution: The following test simulates a real fire condition and may activate
the extinguishing system or other alarms. If this is not desired,
disconnect/inhibit them before the test and reconnect after the simulation.

To simulate a fire:

1

Aim the Fire Simulator towards the detector’s Target Point

Figure 16: 40/40I IR3 Detector Target Point

2

When testing keep a distance of at least 50 cm (20 inches) from the
detector.

3

Press the operation button once. Fire simulation lasts for 20 seconds.
The detector sends an alarm signal (solid red LED).

Target Point

Advertising