4.5 Configuration examples
4.5.1
On-Off controller / Signaller (inverse)
ConF / Cntr: SP.Fn = 0
set-point /cascade controller
C.Fnc = 0
signaller with one output
C.Act = 0
inverse output action
(e.g. heating applications)
ConF /
Out.1: O.Act = 0
output action
Out.1 direct
Y.1
=
1
control output Y1 active
PArA / Cntr:HYS.L
= 0...9999
switching difference below
SP
PArA / Cntr:HYS.H
= 0...9999
switching difference above
SP
PArA / SEtP:SP.LO
= -1999...9999
lower set-point limit for Weff
SP.Hi
= -1999...9999
upper set-point limit for Weff
g
For direct signaller action, the controller action must be changed
(
ConF / Cntr / C.Act = 1 )
Configuration level
KS50/52-1
41
Configuration examples
InH.1
InL.1
SP.LO
SP
SP.Hi
100%
0%
Out.1Â
InP.1Ê
HYS.H
HYS.L
setpoint
relay
output
process value