West Control Solutions N8080 (for 2xxx) User Manual

Page 15

Advertising
background image

OM091-3

Volume I

3-4

59136

Identifier Hex.

Parameter

Adjustment Range

:

3A Process Variable

Read Only (

19999 to 9999)

;

3B Total value

Read Only (

19999 to 9999)

<

3C Maximum Process Variable Read Only (

19999 to 9999)

=

3D

Minimum Process Variable

Read Only (

19999 to 9999)

>

3E Elapsed Alarm 1 Time

Read Only (0 to 60000)

@

40 Reset Max. PV

Write resets; Read always 0

A

41 Reset Min. PV

Write resets; Read always 0

B

42 Reset Elapsed Alarm 1 Time Write resets; Read always 0

C

43 Reset Total value

Write resets; Read always 0

D

44 Reset Latched Alarm 1

Write resets; Read always 0

E

45 Alarm 1 value

Range Max. To Range Min.

F

46 Alarm 2 value

Range Max. To Range Min.

G

47 Scaling Point 1

0 to 100.00

H

48 Display Point 1

19999 to 9999

I

49 Scaling Point 2

Scaling Point 1 to 100.00

J

4A Display Point 2

19999 to 9999

Up to a total of 10 Scaling Points and 10 Display Points are available.

Scaling Point 1

Scaling Point 2

Scaling Point 3 etc.

Any Scaling Point set to 100.00% is automatically the last available.

Z

5A

Scaling Point 10

Scaling Point 9 to 100.00

[

5B Display Point 10

19999 to 9999

\

5C Decimal Point Position

0 (00000) to 4 (0.0000)

]

5D Re-transmitted Scale Min.

19999 to Re-trans. Scale Max.

^

5E Re-transmitted Scale Max.

Re-trans. Scale Min. To 99999

_

5F

Process Variable Offset

0 to Range Span

60 Input Filter

0 to 1000 (0.0 to 100.0s)

a

61 Colour

0 to 3 (0 = Red, 1 = Green,

2 = Green/Red, 3 = Red/Green)

b

62 Alarm Lock

0 (lock enabled), 1 (lock disabled)

c

63 Help level

0 (Help enabled), 1 (Help disabled)

Table 3-1 Parameter Identifiers and Adjustment Ranges