Flow 4 mA Setting

When the loop powered option is ordered, the flow rate that corresponds to 4 mA must be set If the current selection is

correct, press the RIGHT arrow to advance to the next parameter If adjustment is required, press ENTER at the FLOW 4MA

prompt The most significant digit will begin to flash The RIGHT arrow moves the active digit one place to the right for each

press of the key The UP arrow increments the active digit one integer for each press of the key When the correct 4 mA flow

rate has been entered, press ENTER to store this value and move to the next parameter

Flow 20 mA Setting

Follow the same programming process as the FLOW 4MA except for the flow rate setting In this case, use the maximum flow

rate for the meter

4-20 mA Calibration

When ordered with a 4-20 mA option, this menu item allows the fine adjustment of the 4-20 mA output The 4 mA setting

is typically between 35…50 To set the 4 mA value, connect an ammeter in series with the loop power supply See

Figure 3

At the 4-20CAL prompt, press ENTER The display will now show a steady NO indication Press the UP arrow to change to a

flashing YES display Press ENTER to access the 4 mA fine adjustment

Pulse Out

Freq. In

4-20 mA

10…30V DC

1…5V DC

1

2

3

4

5

6

+ -

+ -

+ -

JP2

Mag

Input

Pulse

Inuput

TB1

1 2 3 4 5

J2

Keypad

Connector

DC

Figure 3: Typical ammeter connection

4 mA Adjustments

While monitoring the ammeter, adjust the 4 mA value to obtain a 4 mA reading The UP arrow increments the value and the

RIGHT arrow decrements the value When a steady 4 mA reading is obtained on the ammeter, press ENTER to lock in this

value and move to the 20 mA adjustment

20 mA Adjustments

The 20 mA adjustment is performed using the same procedure as the 4 mA adjustment While monitoring the ammeter,

adjust the 20 mA value to obtain a 20 mA reading The UP arrow increments the value and the RIGHT arrow decrements

the value When a steady 20 mA reading is obtained on the ammeter, press ENTER to lock in this value and move to the

next parameter

4-20 mA Test

The monitor contains a diagnostic routine that allows the simulation of mA values between 4-20 to check output tracking At

the 4-20TEST prompt, the arrow keys change the simulated mA output in increments of one mA The ammeter should track

the simulated mA output If a 4-20 mA test is not necessary, press ENTER to move to the next parameter