Automatic store total, Battery replacement, Additional input options – Badger Meter B2800 User Manual

Page 12: Automatic store total 12, Battery replacement 12, Additional input options 12

Advertising
background image

Automatic Store Total

The monitor is equipped with a store total feature that works automatically, saving the current total to flash memory The

frequency of saves depends on the power supply option chosen

Battery Powered:

Once per hour and just before a low battery condition turns the unit off

Loop Powered:

Once every ten minutes

BATTERY REPLACEMENT

Battery powered monitors use a single 1 5V, “D” size, alkaline battery When replacement is necessary, use a clean fresh

battery to ensure continued trouble-free operation It is recommended that the total be saved to memory before the battery

is removed
Unscrew the two captive screws on the front panel to gain access to the battery Replace the battery, being sure to observe

the proper polarity, and then refasten the front panel

ADDITIONAL INPUT OPTIONS

The B2800 flow monitor is capable of receiving magnetic pickup input (small signal sine wave) or a contact closure input

(pulse) Since most Blancett turbine flow meters utilize a magnetic pickup, the B2800 Flow monitor is shipped configured

for magnetic pickup input To change to a contact closure input, remove JP2 from the top two pins and jumper them to the

bottom two pins See

Figure 5

+ Pulse In

Magnetic Pickup

10K

30V DC (Max)

20 mS Pulse

R

MAX

=

(Loop Supply Voltage - 5)

0.02

1

2

3

4

5

6

+ -

+ -

+ -

- Pulse In

10…30V DC

- Common

Pulse Input Card

Analog Input Card - 4-20 mA

Figure 4: Wiring diagram

Flow Monitor, B2800 Flow Monitor – Advanced

Page 12

November 2013