Connection, Connection 6 – Badger Meter Converters User Manual

Page 6

Advertising
background image

CONNECTION

The 4…20 mA output can drive auxiliary devices (resistive loads) such as displays, recorders and computers, provided that the

voltage supplied by the power supply is adequate Devices must be wired in series with the F to I converter and power supply

The voltage drop across the load(s) and the 6V DC minimum needed to drive the F to I converter determine the minimum

voltage required from the power supply
Determine the necessary voltage required to adequately drive the F to I converter and auxiliary device(s)
The F to I converter acts as a current controlling device Thus, the current output remains the same even if the power supply

voltage fluctuates or the load resistance changes The current varies only with respect to the flow rate from the turbine flow

meter, as long as the voltage drop across the F to I converter is at least 6V DC
The load(s) in the circuit will generally have some electrical resistance, 100 ohms for this example The 4…20 mA loop current

will produce a voltage drop across each load The maximum voltage drop across a load(s) will exist when the loop current is

20 mA The power supply must provide enough voltage for the load(s) plus the 6V DC minimum insertion loss of the

F to I converter

OTEE:

N

See examples on

Power Supply Calculations on page 7

Refer to the wiring diagram in

Figure 1

or

Figure 2

that corresponds to the converter that you have selected for your

application

1

3

2

4

5

BA

4-20 mA

Loop

Powe

r

+

1

3

2

4

5

BA

0…5V DC

Output

10…26V DC

Input

Gnd.

1

3

2

4

5

No Connection

4-20 mA (-)

4-20 mA (+)

Turbine

Pickup

1

3

2

4

5

10…26V DC Input

0…5V DC Output

Ground

Turbine

Pickup

Figure 1: F to I wiring diagram

Figure 2: F to V wiring diagram

Signal Conditioner, Intelligent Frequency Converter

Page 6

November 2013

Advertising