Converter

24V DC

Power

Supply

4…20 mA

1000

Ohms

Figure 5: Power supply calculation example 2

Known values are:

Total Load Resistance

=

1000 Ω

Power Supply

=

24V DC

At 20 mA loop current, the voltage drop across the load(s) is:

1000 Ω x 20 mA = 20,000 mV (20 Volts)

Subtract 20 volts from the 24 volt source to determine that 4 volts is available to power the F to I converter The 4 volts is

below the specified 10…30 volt range and is not sufficient to power the F to I converter
In this instance either the supply voltage must be increased of the load resistance decreased

Signal Conditioner, Intelligent Frequency Converter