Badger Meter Converters User Manual

User manual, Sensor/transducer, F-to-v or f-to-i active sensor

Advertising
background image

INPUT

: 10 - 30 VDC

OUTPUT

: 4 - 20 mA

MAX INPUT

CURRENT

: 25 mA

NEMA

4X,

TEMP

CODE

T6

USE IN CLASS I, GROUPS B, C & D,

CLASS II, GROUPS E, F & G,

CLASS III

MADE IN USA

INTRODUCTION

The Blancett Active Sensor is a state-of-the-art, digital signal processing

device designed to provide exceptional accuracy at a very affordable

price. Designed for use with turbine meters, the sensor measures and

calculates the flow rate to produce an analog current or voltage output

representative of the meter’s flow rate.
The Active Sensor is offered in two versions with a wide range of

compatible turbine flow sensors:

The F-to-I converter provides a 4…20 mA output in a two wire, loop

powered configuration.

The F-to-V converter offers a 0…5V DC output for those applications

where a Voltage output is preferred.

Can be used with Blancett 1100, QuikSert, and FloClean series

turbine flow sensors.

OPERATING PRINCIPLE

Fluid entering the meter passes through the inlet flow straightener which

reduces its turbulent flow pattern and improves the fluid’s velocity profile.

Fluid then passes through the turbine, causing it to rotate at a speed

proportional to the fluid velocity. As each turbine blade passes through

the magnetic field at the base of the magnetic pickup, an AC Voltage pulse

is generated in the pickup coil (see

Figure 1

). These pulses are converted

to either a current or Voltage that is proportional to the volumetric flow

through the meter.

ACTIVE PICK-UP

METER BODY

INPUT: 10 - 30 VDC

OUTPUT: 4 - 20 mA

MAX INPUT CURRENT: 25 mA

NEMA 4X, TEMP CODE T6

USE IN CLASS I, GROUPS B, C & D,

CLASS II, GROUPS E, F & G,

CLASS III

MADE IN USA

INPUT

: 10 - 30 VDC

OUTPUT

: 4 - 20 mA

MAX INPUT

CURRENT

: 25 mA

NEMA

4X,
TEMP

CODE

T6

USE IN CLASS I, GROUPS B, C & D,

CLASS II, GROUPS E, F & G,

CLASS III

MADE IN USA

ACTIVE

PICK-UP

TURBINE

ROTOR

OUTPUT

SIGNAL

Figure 1: Schematic illustration of electric signal generated by rotor movement

Figure 2: Typical turbine flow meter with active sensor installed

SPECIFICATIONS

Power
Frequency to Current (F-to-I)

Loop powered, 6 V insertion loss maximum 10…30V DC supply range

Frequency to Voltage (F-to-V)

10…30V DC supply range (3-wire output)

Inputs

Magnetic Pickup

Frequency

0…3500 Hz

Trigger Sensitivity

30 mV

p-p

Frequency Measurement Accuracy

±1%

Analog Output

4…20 mA current loop

Resolution

1:4000

Temperature Drift

50 ppm / °C (max)

Linearization

10 point using IFC programming utility (PN B220-953)

Threads

5/8-18 UNF

Environmental

Ambient Temperature

–22…158° F (–30…70° C)

Humidity

0…90% non-condensing

Sensor/Transducer

F-to-V or F-to-I Active Sensor

SEN-UM-00084-EN-02 (July 2014)

User Manual