INTRODUCTION

The Blancett K Factor Scaler is a field adjustable frequency divider, which converts the output signal from a turbine meter

or like device with a magnetic pickup or pulse output to an input compatible with a PLC, RTU, CPU data acquisition card or

similar totalizer device The adjustable frequency divisor, referred to as a K factor, allows pulses sent from a turbine meter to

accumulate into a unit recognizable by an end device, such as a PLC, for counting and display
The use of different K factor values allows the device to display in any number of volumetric measurements such as gallons,

cubic meters, liters, barrels, and like units The calibration sheet usually provided with a turbine meter lists a nominal K factor

tested to a specific volumetric flow rate The K factor when placed into the K Factor Scaler provides an output pulse for

each unit of volume that passes through the turbine Any units of volume are possible by recalculating the K factor with the

appropriate conversion factor
In addition, if the K factor is set to one, the K Factor Scaler becomes a preamplifier converting the frequency from a low output

level turbine meter to the logic level needed by a PLC or CPU data acquisition card
The programmable K Factor Scaler provides a lower cost alternative to the Blancett model B220-880 K Factor Scaler The

programmable version uses fewer components, reducing the size of the board and enclosure

OPERATING PRINCIPLE

Fluid passing through the turbine causes it to rotor to spin at a speed proportional to the fluid velocity As each rotor blade

passes through the magnetic field, the blade generates an AC voltage pulse in the pickup coil at the base of the magnetic

pickup (see

Figure 1

) These pulses produce an output frequency proportional to the volumetric flow through the meter The

output frequency with further processing represents flow rate and/or totalization of fluid passing through the flow meter

Turbine Rotor

Magnetic Pickup

or

Other Frequency

Output Device

Output

Signal

Figure 1: Schematic illustration of electric signal generated by rotor movement

The K Factor Scaler input amplifier modifies the signal generated by the turbine The amplifier sends the modified signal to an

onboard microcontroller, which counts pulses up to a predetermined number controlled by the K factor value The range of

the K factor is between 1…999,999,999 The predetermined value once reached triggers a pulse from the output circuitry
The K factor is user adjustable through the programming interface The duration of the output pulse is also selectable At the

end of the output pulse, the internal counters reset to zero and the process starts over

User Manual

Page 5

November 2013