Note #1:
Badger Meter flow sensor K and Offset information is printed in the flow sensor owners manual,
and also available on our website. Calibration constants for other sensors must be supplied by the
manufacturer.

Note #2
Typically the Temperature measured by T1 will be greater than T2 in a heating application and
less than T2 in a cooling application. The selection of one of these choices will determine if energy
calculations are made for heating only (T1>T2), cooling only (T1<T2), or both (absolute).

Note #3
The filter coefficient screen allows adjustment of the flow and energy filters. A scale of 0-10 is used
with 10 providing the greatest degree of smoothing. See the dialog box below.

8. Program using diagram below as a reference.

Step 1

see note #1

Select the flow sensor type
(sine or pulse) and enter the
K and Offset -

Step 4
Select the desired flow
rate and total units here
(see special note #2)

Step 7
Press send to transmit
calibration data to the
Series340

Step 5
Select the desired energy
rate and total units here
(see special note #2)

Step 2
Select the desired temperature
sensor units

Step 3

see note #2

Typically:

Select the method of computing the
temperature differential

T1>T2 for Heating

T1<T2 for Cooling

Step 6
Select the output units per
pulse, and the pulse width

Press to restore the factory
default settings to the screen
Note: Must press “send” before
values take effect.

Step 8
Press to exit parameters screen
and to go back to main screen

Press to refresh the parameters screen with
the current 430 settings.

See Note #3