Badger Meter 7500 Series Mag Meter User Manual

Page 4

Advertising
background image

4

ELECTRICAL CONNECTIONS

The Magnetoflow

®

7500P electronic converter is enclosed in

a water tight (NEMA 4) aluminum enclosure. A pair of 1/2"
NPT water-tight cord grips is provided for the electrical con-
nections.

Do not remove these cord grips unless you replace them with
water-tight conduit adapters or similar connectors. Failure to

comply with this requirement will void the Badger Meter, Inc.
warranty. To access the electrical connection, remove the cover
of the amplifier by loosening the four (4) mounting screws.

For all wiring, use 18 or 20 Awg wire.

• This connection shown above is for Batch Panels that require a 115VAC hot pulse for meter signals.

• It is recommended that the Batch Panel Manufacturer be consulted to confirm the required pulse signal.

• For a 115VAC neutral pulse signal to Batch Panel simply take T-2 Jumper to 115 neutral power supply.

POWER SUPPLY CONNECTION

Ground

Neutral 115 VAC
Hot 115 VAC

Ground

Neutral 115 VAC

Hot 115 VAC

CONNECTING MODEL 7500P TO 110 VAC FROM BATCH CONTROL PANEL POWER SUPPLY.

(TYPICAL CONCRETE BATCH PANEL)

T

2

T

1

BATCH PANEL
Ground

Neutral 115 VAC
Hot 115 VAC

Meter Pulse Input

DC-Switched

Common

Ground

Neutral 115 VAC

Hot 115 VAC

Open Collector
Transistor Output

Solid State

Relay Output